Installation guide, Amp1h5 – GE Industrial Solutions AMP1H5 User Manual

Page 19

Advertising
background image

TM

AMP1H5

INSTALLATION GUIDE

ZL0115-0A

PAGE 19

©2013 For technical support please contact

01132

DET-785

our GE tech support team at 1-800-GE-1-STOP (1-800-431-7867)

#

Object_Name

Description

R/W

NV

Units

Range

Additional information

AI16

Volts_BC

Voltage Phase B-C

R

Volts

AI17

Volts_AC

Voltage Phase A-C

R

Volts

AI18

Volts_AN

Voltage Phase A-N

R

Volts

AI19

Volts_BN

Voltage Phase B-N

R

Volts

AI20

Volts_CN

Voltage Phase C-N

R

Volts

AI21

Current_A

Current Phase A

R

Amps

AI22

Current_B

Current Phase B

R

Amps

AI23

Current_C

Current Phase C

R

Amps

AI24

Reserved_AI24

Reserved

R

n/a

Returns QNAN or any value

AI25

Frequency

Frequency

R

Hz

45.0-65.0

Returns QNAN if frequency is out of range (or no voltage

input present on Phase A)

AI26

kVAh

Apparent Energy

Consumption

R

NV

kVAh

0 - 3.4+E38

The UNITS property of object AI26 reports that these

units are kWh because there is no unit type in the

BACnet standard for kVAh.

AI27

kVARh

Reactive Energy

Consumption

R

NV

kVARh

0 - 3.4+E38

The UNITS property of object AI27 reports that these

units are kWh because there is no unit type in the

BACnet standard for kVARh.

AI28

kVA_A

Apparent Power

Phase A

R

kVA

0 - Max_Power (AI45)

AI29

kVA_B

Apparent Power

Phase B

R

kVA

0 - Max_Power (AI45)

AI30

kVA_C

Apparent Power

Phase C

R

kVA

0 - Max_Power (AI45)

AI31

KVAR_A

Reactive Power

Phase A

R

kVAR

0 - Max_Power (AI45)

AI32

KVAR_B

Reactive Power

Phase B

R

kVAR

0 - Max_Power (AI45)

AI33

KVAR_C

Reactive Power

Phase C

R

kVAR

0 - Max_Power (AI45)

AI34

KW_Present_

Demand

Total Real Power

Present Demand

R

kW

0 - Max_Power (AI45)

AI35

KVAR_Present_

Demand

Total Reactive Power

Present Demand

R

kVAR

0 - Max_Power (AI45)

AI36

KVA_Present_

Demand

Total Apparent

Power Present

Demand

R

kVA

0 - Max_Power (AI45)

AI37

KW_Max_

Demand

Total Real Power

Maximum Demand

R

NV

kW

0 - Max_Power (AI45)

This retains the largest value measured for Total Real

Power Demand (AI34) for any single demand interval

since the Max Demand were last explicitly reset via

AV1 (this is also reset when the demand interval is

changed).

AI38

KVAR_Max_

Demand

Total Reactive Power

Maximum Demand

R

NV

kVAR

0 - Max_Power (AI45)

This retains the largest value measured for Total

Reactive Power Demand (AI35) for any single demand

interval since the Max Demand were last explicitly

reset via AV1 (this is also reset when the demand

interval is changed).

AI39

KVA_Max_

Demand

Total Apparent

Power Maximum

Demand

R

NV

kVA

0 - Max_Power (AI45)

This retains the largest value measured for Total

Apparent Power Demand (AI36) for any single demand

interval since the Max Demand were last explicitly

reset via AV1 (this is also reset when the demand

interval is changed).

Advertising