AMP1H5

INSTALLATION GUIDE

ZL0115-0A

PAGE 6

©2013 For technical support please contact

01132

DET-785

our GE tech support team at 1-800-GE-1-STOP (1-800-431-7867)

CONTROL POWER

Direct Connect Control Power (DC Control Power)

L1

N

L2 L3

1 2

G

L1

N

L2 L3

1 2

G

L1

1 2

G

L2 L3

Direct Connect Control Power (Line to Neutral)

Line to Neutral from 90 VAC to 347 VAC (UL) or 300 VAC (CE)

1 2

G

Control Power Transformer (CPT) Connection

Direct Connect Control Power (Line to Line)

Line to Line from 90 VAC to 600 VAC (UL) (520 VAC for CE). In UL installations the lines may be

floating (such as a delta). If any lines are tied to an earth (such as a corner grounded delta), see the

Line to Neutral installation limits. In CE compliant installations, the lines must be neutral (earth)

referenced at less than 300 VAC

L-N

The Control Power Transformer may be wired L-N or L-L. Output to meet meter input requirements

DC Control Power from 125 VDC to 300 VDC (UL and CE max.)

Fuse Recommendations:

Keep the fuses close to the power source (obey local and national code requirements).

For selecting fuses and circuit breakers, use the following criteria:

• Select current interrupt capacity based on the installation category and

fault current capability.

• Select over-current protection with a time delay.
• Use a voltage rating sufficient for the input voltage applied.
• Provide overcurrent protection and disconnecting means to protect

the wiring. For DC installations, provide external circuit protection.
Suggested: 0.5A, high-interrupt capability time delay fuses rated for DC
operation at or above the supply voltage.

• The earth connection is required for electromagnetic compatibility (EMC)

and is not a protective earth ground.