Installation guide, Rs-485 communications, Bacnet default settings – GE Industrial Solutions AMP1H5 User Manual

Page 13: Amp1h5

Advertising
background image

TM

AMP1H5

INSTALLATION GUIDE

ZL0115-0A

PAGE 13

©2013 For technical support please contact

01132

DET-785

our GE tech support team at 1-800-GE-1-STOP (1-800-431-7867)

RS-485 COMMUNICATIONS

Daisy-chaining Devices to the Power Meter

The RS-485 slave port allows the power meter to be connected in a daisy chain with
up to 63 2-wire devices.

+

S

120 Ω terminator on the first and last device

of the daisy chain

Shield wire

NOTES:

• The terminal’s voltage and current ratings are compliant with the

requirements of the EIA RS-485 communications standard.

• The RS-485 transceivers are ¼ unit load or less.
• RS-485+ has a 47 kΩ pull up to +5V, and RS-485- has a 47 kΩ pull down

to Shield (RS-485 signal ground).

• Wire the RS-485 bus as a daisy chain from device to device, without

any stubs. Use 120 Ω termination resistors at each end of the bus (not
included).

• Shield is not internally connected to Earth Ground.
• Connect Shield to Earth Ground somewhere on the RS-485 bus.

For all terminals:

• When tightening terminals, apply the correct torque: 0.37 to 0.44 ft·lb

(0.5 to 0.6 N·m).

• Use 14-24 gauge(2.1-0.2 mm

2

) wire for all connections.

BACNET DEFAULT SETTINGS

Setting

Default Value*

BACnet Object

Setup Password

00000

n/a

Reset Password

00000

n/a

System Type

40 (3 + N) Wye

AV2

CT Primary Ratio

200 A

AV3

CT Secondary Ratio

0.33 V

AV4

PT Ratio

1:1 (none)

AV5

System Voltage

480 V L-L

AV6

Max. Theoretical Power

Calculated from AV2, AV3,

AV5 & AV6 (with all default

settings, this would be

103.92 kW)

AI45

Display Mode

1 (IEEE Units)

AV7

Phase Loss Voltage

Threshold

10% of System Voltage

AV8

Phase Loss Voltage

Threshold

25% Phase to Phase

Imbalance

AV9

Demand: number of

subintervals per interval

1 (block mode)

AV10

Demand: sub-interval

length

900 sec (15 min)

(AV11 default value is

90000 [1/100 seconds])

AV11

BACnet MAC Address

001

n/a

BACnet MS/TP Baud Rate

76.8 kBaud

n/a

BACnet MS/TP Max_Master 127

Device

BACnet Device_ID

Pseudo-random value

from 1,000,000 to

3,097,151

Device

BACnet Device Location

Installed location not yet

identified

Device

Trend_Log Object 1

Log_Device_Object_

Property

AI1 (Real Energy)

TL1

Trend_Log Object 2

Log_Device_Object_

Property

AI27 (Reactive Energy)

TL2

Trend_Log Object 3

Log_Device_Object_

Property

AI34 (Total Real Present

Demand)

TL3

* Default values are preset at the factory. Once changed, there is no way to automatically reset
defaults. They must be restored individually. The baud rate and MAC address are set through the
user-interface screens, and the others are set by re-writing each Object (see BACnet Programming
Information section, next page).

Red

Black

Gray

0.37–0.44 ft•lb

(0.5–0.6 N•m)

Use 14-24 gauge wire