Warning, Installation guide, Wiring diagrams – GE Industrial Solutions AMP1H5 User Manual

Page 5: Amp1h5, Diagram 3: 1-phase direct voltage connection 2 ct

Advertising
background image

TM

AMP1H5

INSTALLATION GUIDE

ZL0115-0A

PAGE 5

©2013 For technical support please contact

01132

DET-785

our GE tech support team at 1-800-GE-1-STOP (1-800-431-7867)

N L1

X2

X1

White

Black

A

B

C

N

+

-

+

-

+

-

A

B

C

Diagram 1: 1-Phase Line-to-Neutral 2- Wire System 1 CT

Diagram 2: 1-Phase Line-to-Line 2-Wire System 1 CT

L1 L2

X2

X1

X2

X1

A

B

C

N

+

-

+

-

+

-

A

B

C

N

White

Black

White

Black

L1 L2

X2

X1

A

B

C

N

+

-

+

-

+

-

A

B

C

White

Black

Diagram 3: 1-Phase Direct Voltage Connection 2 CT

L1 L2 L3

X2

X1

A

B

C

N

A

B

C

X2

X1

X2

X1

+

-

+

-

+

-

White

Black

White

Black

White

Black

L1

N

L2 L3

X2

X1

A

B

C

N

A

B

C

X2

X1

X2

X1

+

-

+

-

+

-

White

Black

White

Black

White

Black

Diagram 4: 3-Phase 3-Wire 3 CT no PT

Diagram 5: 3-Phase 4-Wire Wye Direct Voltage Input Connection 3 CT

USE SYSTEM TYPE 11 (2L)

USE SYSTEM TYPE 12 (2L + 1n)

USE SYSTEM TYPE 31 (3L)

USE SYSTEM TYPE 40 (3L + 1n)

USE SYSTEM TYPE 10 (1L + 1n)

White

Black

White

Black

White

Black

L1

N

L2 L3

X2

X1

A

B

C

N

A

B

C

X2

X1

X2

X1

+

-

+

-

+

-

Diagram 6: 3-Phase 4-Wire Wye Connection 3 CT 3 PT

USE SYSTEM TYPE 40 (3L + 1n)

WIRING DIAGRAMS

RISK OF ELECTRIC SHOCK OR PERMANENT EQUIPMENT DAMAGE

CT negative terminals are referenced to the meter’s neutral and may be at elevated voltages
· Do not contact meter terminals while the unit is connected
· Do not connect or short other circuits to the CT terminals

Failure to follow these instructions may cause injury, death or equipment damage.

WARNING

Advertising