Installation guide, Amp1h5 – GE Industrial Solutions AMP1H5 User Manual

Page 18

Advertising
background image

TM

AMP1H5

INSTALLATION GUIDE

ZL0115-0A

PAGE 18

©2013 For technical support please contact

01132

DET-785

our GE tech support team at 1-800-GE-1-STOP (1-800-431-7867)

#

Name

Description R/W

NV

Units

Range

Factory

Default

Value

Additional information

AV9

Phase_

Loss_

Imbalance_

Threshold

Phase Loss

Imbalance

Threshold

R/W

NV

Percent

1-99

25

Phase Loss Imbalance Threshold in Percent. Default is 25% phase to phase difference.

For a 3-phase Y (3 + N) system type (40 in object AV2), both Line to Neutral and Line

to Line voltages are tested. In a 3-phase ∆ System type (31 in object AV2), only Line

to Line voltages are examined. In a single split-phase (2 + N) system type (12 in

object AV2), only the line to neutral voltage are compared.

AV10 Subintervals Number of

Subintervals

Per Demand

Interval

R/W

NV

1-6

1

Number of Sub-Intervals per Demand Interval. Sets the number of sub-intervals that

make a single demand interval. For block demand, set this to 1. Default is 1. When

Sub-Interval Length (in object AV11) is set to 0 (sync-to-comms mode), the meter

ignores this value.

AV11 Subinterval_

Length

Subinterval

Length

R/W

NV

hundreths

of a

second

0,

10-32767

90000

Sub-Interval Length in hundredths of a second. For sync-to-comms mode, which

allows manual triggerring of demand intervals and the logging of another Trend_

Log record, set this value to 0 and write 21211 to the reset register (object AV1) each

time the sub-interval must be externally reset. Default is 90000 (15 minutes). This

variable is tied directly to the Log_Interval property of all three Trend_Log objects

(their value is always the same as this one). Changing any of these four properties

changes all of them.

Analog_Input Objects

Use the Present_Value property of the Analog_Input objects for all read-only numeric variables in the meter other than those used specifically for device configuration (in the
Device Object) or data logging (in the Trend_Log objects).

These objects support the Description and Reliability object properties and all required Analog_Input object properties. None of them are writable. The values that are not
instantaneous (i.e., Accumulated Energy, Max Demand, Pulse Input Counts) are non-volatile. They are not updated while control power is inactive, but their past values are
retained when power is restored.

For complete assurance, check the Reliabilty property for a No_Fault_Detected status before reading the Present_Value. If the line voltage or input frequency of the system
being monitored falls out of the supported range, the corresponding alert bits (BI1-BI7) are set and the reliability property of any values that cannot be accurately measured
under those conditions returns Unreliable_Other.

#

Object_Name

Description

R/W

NV

Units

Range

Additional information

AI1

Energy

Real Energy

Consumption

R

NV

kWh

0 - 3.4+E38

AI2

kW_Total

Total Real Power

R

kW

0 - Max_Power (AI45)

AI3

kVAR_Total

Total Reactive Power R

kVAR

0 - Max_Power (AI45)

AI4

kVA_Total

Total Apparent

Power

R

kVA

0 - Max_Power (AI45)

AI5

PF_Total

Total Power Factor

R

Power

Factor

0.00 - 1.00

1.00 for 100%

AI6

Volts_LL_Avg

Voltage L-L Average

R

Volts

AI7

Volts_LN_Avg

Voltage L-N Average

R

Volts

AI8

Current_Avg

Current Average

R

Amps

AI9

kW_A

Real Power Phase A

R

kW

0 - Max_Power (AI45)

AI10

kW_B

Real Power Phase B

R

kW

0 - Max_Power (AI45)

AI11

kW_C

Real Power Phase C

R

kW

0 - Max_Power (AI45)

AI12

PF_A

Power Factor

Phase A

R

Power

Factor

0.00 - 1.00

1.00 for 100%

AI13

PF_B

Power Factor Phase B R

Power

Factor

0.00 - 1.00

1.00 for 100%

AI14

PF_C

Power Factor Phase C R

Power

Factor

0.00 - 1.00

1.00 for 100%

AI15

Volts_AB

Votlage Phase A-B

R

Volts