TM

AMP1H5

INSTALLATION GUIDE

ZL0115-0A

PAGE 23

©2013 For technical support please contact

01132

DET-785

our GE tech support team at 1-800-GE-1-STOP (1-800-431-7867)

Trend_Log Properties

Used

R/W

Units

Additional information

Stop_Time

W

Date/Time

Sets the Date/Time when data Logging will STOP (if still running).

Stop_Time will be ignored if “”wildcard”” values are used in any of the fields.

Log_Device_Object_

Property

W

BACnetDeviceObjectProptertyReference Set (point) this to the Present_Value of any of objects AI1 through AI49

to establish which parameter to log. Default values are:

TL1 = Real Energy Consumption (Array of AI1 Present_Value)

TL2 = Reactive Energy Consumption (Array of AI27 Present_Value)

TL3 = Total Real Power Present Demand (Array of AI34 Present_Value)

Log_Interval

W

0.01 seconds

Logging period in hundredths of a second.

Default is 90000 (15 minute intervals); minimum value is 1000 (10 seconds). This property can

also be set to Zero, which will change all three Trend_Logs and the Demand calculation to a

manual mode (sometimes referred to as “Sync to Comms”. In manual mode, the demand interval

is updated and another record is logged upon a manual command, which is issued by writing the

value 21211 to the Present_Value of object AV1.

Stop_When_Full

W

Binary

Set this to TRUE to stop logging when the buffer is full (single-shot mode) or FALSE to continue

when full (wrap & overwtrite oldest data entries).

Buffer_Size

R

5760

Length of Log Data buffer (# of records).

Log_Buffer

R

List of BACnetLongRecord

Contains the data values logged, with timestamps

Record_Count

W

Unsigned 32-bit integer

This is an integer count of how many records logged since the Trend_Log objects were last reset.

Writing a Zero to this property resets the logs of all three objects. This value defaults to Zero, but,

by default, logging will start automatically at 15 minute intervals.

Total_Record_Count

R

Unsigned 32-bit integer

This is an integer count of how many records logged since the Trend_Log objects were created (the

factory state of the meter). This count is unaffected by resetting the Record Count or by power

failures.

Event_State

R

Binary