Operation and features, Zenith module 9 accessory package – GE Industrial Solutions ZTSH SERIES 30-4000 AMPS User Manual

Page 11

Advertising
background image

Zenith Controls, Inc.

9

ZTSH Operation and Maintenance Manual (43R-1000)

Zenith Module 9 Accessory Package

The Zenith Module 9 Accessory package includes nine of the commonly specified accessories.

These accessories are:

A

Auxiliary Contacts:

A3

Closed when switch is in emergency position

L

Indicating LED Pilot Lights:

L1

Indicates switch in emergency position

L2

Indicates switch in normal position

P1

Time Delay - Engine Start: Adjustable 0.5 to 6 seconds

T200 Time Delay on Retransfer to Normal: To delay retransfer to normal source (immediate

retransfer on generator set failure); standard setting 30 minutes, adjustable 0-60 minutes.

T100 Time Delay on Retransfer to Normal: To delay retransfer to normal source (immedi-

ate retransfer on generator set failure); standard setting 30 min., adjustable 0-30 min.

T3/W3Time Delays - Presignal for Auxiliary Control: Prior to transfer between two live

sources in either direction, provides an adjustable (factory set at 20 second) presig-

nal contact closure

U200 Time Delay for Engine Cooldown: Allows engine to run unloaded after switch

retransfers to normal. Standard setting 5 min., adjustable 0-60 minutes.

U100 Time Delay for Engine Cooldown: Allows engine to run unloaded after switch

retransfer to normal; standard setting 5 min., adjustable 0-5 min.

W200 Time Delay on Transfer to Emergency: To delay transfer to emergency after nor-

mal source failure; standard setting 1 sec., adjustable 0-5 minutes.

W100 Time Delay on Transfer to Emergency: To delay transfer to emergency after verifying

emergency source available; standard setting 1 sec., adjustable 0-15 sec.