Engine, Installation, A3-2 – GE Industrial Solutions ZTSH SERIES 30-4000 AMPS User Manual

Page 6: Control connections

Advertising
background image

Control Connections

A complete information package is furnished with each

transfer switch including a complete connection diagram

and schematic which details all necessary control circuit

field connections.

The engine start control wires connect to the terminals

specified in the upper left corner of the control panel.

Figure 2 shows the location of these terminals on the stan-

dard SSRCP printed circuit board mounted on the steel

backplate. These terminals are clearly identified by a pre-

printed label attached to the steel control panel. In the

case of manual transfer switches, or in other applications

not requiring the standard control panel, clearly marked

terminal blocks are provided in the upper left corner of

the control panel for the engine start control wires.

Terminals for field connections to the A3 Emergency auxil-

iary contacts and the A4 Normal auxiliary contacts are also

provided. These terminals are clearly marked and appear on

the side of the power panel. On 400 amp units these terminals

appear on the disconnect switch bracket above the operator

handle, and are marked as illustrated in Figure 3.

Figure 2

ENGINE

A3-2

4

Zenith Controls, Inc.

ZTSH Operation and Maintenance Manual (43R-1000)

Installation

(cont’d)

Figure 3

Table 1

Screw Type Terminals for External Power Connections

Switch Size

(Amps)

40

80

100

150

225

260

400

600

800

Normal, Emergency & Load Terminals

1

#8 to 2 AWG

Cable Per Pole

Range of Wire Sizes

1000

1200

1600
2000
3000
4000

1

#8 to 1/0 AWG

1

#8 to 1/0 AWG

1

#8 to 3/0 AWG

1

#6 AWG to 250 MCM

1

#6 AWG to 350 MCM

1

#4 AWG to 600 MCM

2

#2 AWG to 600 MCM

4

#2 AWG to 600 MCM

Fully Rated Neutral Bar (When Required)

3

#8 to 1/0 AWG

No. of Cables

Range of Wire Sizes

3

#8 to 1/0 AWG

3

#8 to 1/0 AWG

3

#6 AWG to 300 MCM

3

#6 AWG to 300 MCM

3

#6 AWG to 300 MCM

4

#2 AWG to 600 MCM

8

#2 AWG to 600 MCM

12

#2 AWG to 600 MCM

4

#2 AWG to 600 MCM

12

#2 AWG to 600 MCM

4

#2 AWG to 600 MCM

12

#2 AWG to 600 MCM

Line and load terminals are located
in rear and arranged for bus bar
connection.

12
12
12
12

3/0 AWG to 750 MCM
3/0 AWG to 750 MCM
3/0 AWG to 750 MCM
3/0 AWG to 750 MCM