Appendix b - replacement parts – GE Industrial Solutions ZTSH SERIES 30-4000 AMPS User Manual
Page 35
■
■
33
Zenith Controls, Inc.
■
■
ZTSH Operation and Maintenance Manual (43R-1000)
APPENDIX B - REPLACEMENT PARTS
(Continued)
6.
OPTIONAL CONTROL PANEL
P1
B3
B2
B1
VFSM
T
U
W
RT
CR
CE1
CN1
XN
XE
TAG
DESCRIPTION
VOLTAGE 50/60 HZ
PART NUMBER
XN, XE
Control Transformers
(See Note 1)
120 V
K-3068
208 V
K-3053
240 or 480 V
K-3041
416 V
K-1055 (K-1185)
B 1, 2, 3
Phase Relays Electro-Mechanical-Standard
Solid State
(See Note 1)
120 V
K-1056 (K-1186)
208 or 240 V
K-1058 (K-1188)
480 V
K-1186
VFSM
Voltage Frequency Sensor
120 V
K-1192
CR
Control Relay
120 V
Y-260002
RT
Bypass T Relay
120 V
Y-260002
CN1, CE1 or
CCN, CCE
Transfer Relays
ZTSH 4-40, ZTSH 160-300
K-1120
120 V
ZTSH 60-120
K-1095
120 V
T
Time Delay-to-Normal, Timer Solid State
0.1 sec. to 100 hours; adjustable
K-1230
120 V
U
Engine Cool Down, Timer Solid State
0.1 sec. to 100 hours; adjustable
K-1230
120 V
W
Time Delay Emergency, Timer Solid State
0.1 sec. to 100 hours; adjustable
K-1230
120 V
P1
Time Delay Engine Start Timer
0.5 sec. to 6 sec.; adjustable
K-1201
120 V
P2
Optional
0.5 sec. to 300 sec.; adjustable
K-1061
120 V
NOTES: 1. If -6 voltage system (575/600V is supplied, then XN, XE is K-3059 and B1, 2, 3 is K-1155 (120V) supplied with XB (575-600V/120V)
3 phase transformer assembly.