Zenith Controls, Inc.

3

ZTSH Operation and Maintenance Manual (43R-1000)

D

CABINET

LIFTING EYES

SPREADER BAR

H

45°

Figure 1

NOTICE

When lifting the switch using a spreader bar, height H must be equal to half of distance D.

Installation

(cont’d)

Table 2

Tightening Torque for Lugs

Socket Size

Across Flats

Torque

Lb. - In.

Lb. - Ft.

45

1/8

4

100

5/32

8

120

3/16

10

150

7/32

12

200

1/4

17

275

5/16

23

375

3/8

31

500

1/2

42

600

9/16

50

Table 3

Tightening Torque for Bus Bars

Bolt Size

Torque Bolt (Grade 5)

Lb. - In.

Lb. - Ft.

72

1/4-20

6

132

5/16-18

11

300

3/8-16

25

720

1/2-13

60

Power Connections

Zenith transfer switches are supplied with

UL listed solderless screw type terminals

as standard for the Normal, Emergency and

Load power connections. Table 1 lists the

number and sizes of cable lugs supplied

as standard for each switch amp rating.

Connect the Normal, Emergency, and Load

conductors to the clearly marked terminals

on the transfer switch. Remove surface

oxides from cables by cleaning with a wire

brush. Verify that all connections are cor-

rect before tightening the lugs. All cable

lug connections must be tightened to the

proper torque values as shown in Table 2.

Do not run cables or wiring behind front-
connected transfer switches.

In cases where the Normal, Emergency and

Load connections are made to a rear con-

nected bus bar, a compression washer, flat

washer, and a minimum grade 5 bolt must

be used and torqued to the values in Table 3.