Zenith Controls, Inc.

ZTSH Operation and Maintenance Manual (43R-1000)

Operation and Features

(cont’d)

Zenith Optional Accessories

Many control accessories are available to meet specific requirements. Some of the more

commonly specified accessories are:

A

Auxiliary Contacts:

A6

Deenergizes external motor control circuit5 seconds (adjustable) prior to

transfer in either direction.

C

Plant Exerciser (no load): Automatically starts the generator to run unloaded at

selected intervals

C/D Plant Exerciser (Load/no load): Allows the generator to start and run unloaded

or to simulate a power failure, start generator and run under load. Specify weekly,

bi-weekly or calendar schedule

L

Indicating LED Pilot Lights:

L3

Indicates normal source available

L4

Indicates emergency source available

P2

Time Delay - Engine Start: Adjustable 0.5 to 300 seconds

Q2

Peak Shave/Remote Load Test: Input for peakshave or remote load test; includes

automatic return to normal if emergency source fails and normal is present; 120

VAC or 24 VDC

R4

In-Phase Monitor: Prevents transfer until two sources are in relative synchronism

R43

In-Phase Monitor: Prevents transfer until two sources are in relative synchronism

S1

Four-position selector switch (Stop - Hand Crank - Test - Automatic)

S2

Disconnect switch in series with accessory E to disconnect engine-starting circuit

S3

Source selector switch circuit; to select either source as primary

T3/W3Time Delays - Presignal for Auxiliary Control: Prior to transfer between two live

sources in either direction, provides an adjustable (factory set at 20 second) presignal

contact closure

W100 Time Delay on Transfer to Emergency: To delay transfer to emergency after verifying

emergency source available; standard setting 1 sec., adjustable 0-15 sec.

YEN Pushbutton Bypass of T&W Timers