GE Industrial Solutions ZTSH SERIES 30-4000 AMPS User Manual

Page 23

Advertising
background image

ZTSH Operation and Maintenance Manual (43R-1000)

N3

T3

N2

T2

N1

T1

NN

TN

E3

E2

E1

EN

22

21

20

32

31

30

16

15

20

B1

21

22

CCN

32

31

30

E1,2,3,N - EMERGENCY LINE

T1,2,3,N - LOAD

N1,2,3,N - NORMAL LINE

SWITCHED NEUTRAL OR
SOLID NEUTRAL IF REQUIRED

CR

CR

T

B1

B2

B3

CR

C

NC

NO

U

P1

CCN

23

23A

23B

23C

23Z

28

26

28Z

29

J1

J2

J3

J4

J7

CCN - POWER RELAY, ENERGIZES TRANSFER

TO NORMAL SOLENOID

W

RT

W -

TIME DELAY TO EMERGENCY

RT - EMERGENCY CONTROL RELAY

CCE - POWER RELAY, ENERGIZE

VFSM- EMERGENCY VOLTAGE AND

FREQUENCY SENSING RELAY

VFSM

L2

27

RT

J5

T

U

25Z

P1

ENGINE START CONTACT FROM P1

LEGEND

WIRE CONNECTION

WIRE ON MAIN TERMINAL BLOCK

WIRE ON DISCONNECT PLUG

OPTIONAL ACCESSORY

A4

NORMAL

SN

A3

EMERGENCY

MECHANICALLY ACTUATED
NORMAL AND EMERGENCY
POSITION CONTACTS A3 & A4

B2

B3

CE - TRANSFER TO EMERGENCY SOLENOID

CN - TRANSFER TO NORMAL SOLENOID

DS - DISCONNECT SWITCH FOR SERVICE

XN - NORMAL CONTROL TRANSFORMER

XE - EMERGENCY CONTROL TRANSFORMER

UNDER VOLTAGE RELAYS

COM

TS

YN

J8

J6

J9

CR

33Z

37

W

RT

J10

25

24

C

NC

NO

CCE

36

L1

35Z

SE

J11

35

34

33Y

VFSM

33A

33

RT

38

RT

CR

12A

13

11

12

T -

TIME DELAY ON RETRANSFER

CR -

CONTROL RELAY

YN -

PUSH BUTTON TO BYPASS T

L2 -

NORMAL POSITION LIGHT

U -

ENGINE OVER-RUN TIMER

P1 -

TIME DELAY TO ENGINE START

SN -

MECHANICALLY ACTUATED CONTACTS

(NORMAL POSITION)

SE -

MECHANICALLY ACTUATED CONTACTS

(EMERGENCY POSITION)

L1 -

EMERGENCY POSITION LIGHT

CN

206

209

CCE

CE

306

307

DS

NOTE - ZTSH SHOWN IN NORMAL POSITION WITH NO POWER AVAILABLE

NN

EN

14

APPENDIX A - TYPICAL SCHEMATIC DIAGRAM 40 - 260 AMPS