Appendix b - replacement parts, Standard control panel (ssrcp), Continued) – GE Industrial Solutions ZTSH SERIES 30-4000 AMPS User Manual
Page 34
■
■
Zenith Controls, Inc.
32
■
■
ZTSH Operation and Maintenance Manual (43R-1000)
APPENDIX B - REPLACEMENT PARTS
(Continued)
5.
STANDARD CONTROL PANEL (SSRCP)
SPARE
J1 J2 J3 J4 J5 J6 J7 J8 J9 J10 J11
JUMPERS
XE
RT
CR
XN
B1
B2
B3
VFSM
W
U
T
P1
JUMPER
CONNECTS
POINTS
REMOVE WHEN
ACCESSORIES USED
J1
23, 23A
B1
J2
23A, 23B
B2
J3
23B, 23C
B3
J4
23C, 23Z
JIN, TS, C/D
J5
23Z, 27
T, YN
J6
25, 25Z
T3, R4
J7
28, 28Z
S1, C, C/D
J8
28Z, 29
P1 & U
J9
33A, 33Y
ER1, 2, 3, J1E
J10
33Z, 37
W
J11
35, 35Z
R4, W3
TAG
DESCRIPTION
VOLTAGE 50/60 HZ
PART NUMBER
XN, XE
Control Transformers
(See Note 1)
120 V
K-3068
208 V
K-3070
240 or 480 V
K-3071
416 V
K-3089
B 1, 2, 3
Phase Relays
Solid State
(See Note 1)
120 V
K-1185
208 or 240 V
K-1186
480 V
K-1186
VFSM
Voltage Frequency Sensor
120 V
K-1192
CR
Control Relay
120 V
K-1204
RT
Bypass T Relay
120 V
K-1204
CN1, CE1 or
CCN, CCE
Transfer Relays
(Mounted below SSRCP)
ZTSH 4-40, ZTSH 160-300
K-1120
120 V
ZTSH 60-120
K-1095
120 V
T
Time Delay-to-Normal, Timer Solid State
0.1 sec. to 100 hours; adjustable
K-1230
120 V
U
Engine Cool Down, Timer Solid State
0.1 sec. to 100 hours; adjustable
K-1230
120 V
W
Time Delay Emergency, Timer Solid State
0.1 sec. to 100 hours; adjustable
K-1230
120 V
P1
Time Delay Engine Start Timer
0.5 sec. to 6 sec.; adjustable
K-1201
120 V
P2
Optional (Mounted below SSRCP)
0.5 sec. to 300 sec.; adjustable
K-1061
120 V
J1 - J11
Jumpers
PS-5067
NOTES: 1. If -6 voltage system (575/600V is supplied, then XN, XE is K-3087 and B1, 2, 3 is K-1185 (120V) supplied with XB (575-600V/120V)
3 phase transformer assembly.