Zenith Controls, Inc.

32

ZTSH Operation and Maintenance Manual (43R-1000)

APPENDIX B - REPLACEMENT PARTS

(Continued)

5.

STANDARD CONTROL PANEL (SSRCP)

SPARE

J1 J2 J3 J4 J5 J6 J7 J8 J9 J10 J11

JUMPERS

XE

RT

CR

XN

B1

B2

B3

VFSM

W

U

T

P1

JUMPER

CONNECTS

POINTS

REMOVE WHEN

ACCESSORIES USED

J1

23, 23A

B1

J2

23A, 23B

B2

J3

23B, 23C

B3

J4

23C, 23Z

JIN, TS, C/D

J5

23Z, 27

T, YN

J6

25, 25Z

T3, R4

J7

28, 28Z

S1, C, C/D

J8

28Z, 29

P1 & U

J9

33A, 33Y

ER1, 2, 3, J1E

J10

33Z, 37

W

J11

35, 35Z

R4, W3

TAG

DESCRIPTION

VOLTAGE 50/60 HZ

PART NUMBER

XN, XE

Control Transformers
(See Note 1)

120 V

K-3068

208 V

K-3070

240 or 480 V

K-3071

416 V

K-3089

B 1, 2, 3

Phase Relays
Solid State
(See Note 1)

120 V

K-1185

208 or 240 V

K-1186

480 V

K-1186

VFSM

Voltage Frequency Sensor

120 V

K-1192

CR

Control Relay

120 V

K-1204

RT

Bypass T Relay

120 V

K-1204

CN1, CE1 or
CCN, CCE

Transfer Relays
(Mounted below SSRCP)

ZTSH 4-40, ZTSH 160-300

K-1120

120 V

ZTSH 60-120

K-1095

120 V

T

Time Delay-to-Normal, Timer Solid State

0.1 sec. to 100 hours; adjustable

K-1230

120 V

U

Engine Cool Down, Timer Solid State

0.1 sec. to 100 hours; adjustable

K-1230

120 V

W

Time Delay Emergency, Timer Solid State

0.1 sec. to 100 hours; adjustable

K-1230

120 V

P1

Time Delay Engine Start Timer

0.5 sec. to 6 sec.; adjustable

K-1201

120 V

P2

Optional (Mounted below SSRCP)

0.5 sec. to 300 sec.; adjustable

K-1061

120 V

J1 - J11

Jumpers

PS-5067

NOTES: 1. If -6 voltage system (575/600V is supplied, then XN, XE is K-3087 and B1, 2, 3 is K-1185 (120V) supplied with XB (575-600V/120V)

3 phase transformer assembly.

Advertising