background image

Zenith Controls, Inc.

13

ZTSH Operation and Maintenance Manual (43R-1000)

Maintenance and Testing

(cont’d)

Annunciation

Possible Cause

Corrective Action

Engine Does Not STOP

Delay to Engine Stop LED on

Normal Available, Normal Position,
and Emergency Available LEDs on

U timing cycle not complete

Engine start wires not
terminated correctly

Generator in “Manual”

Check U Timer setting

Check Engine Start Connections

Investigate why the Engine Control
Switch was put in manual

Annunciation

Possible Cause

Corrective Action

ATS Will Not Transfer To EMERGENCY

Emergency Available LED off

None

Normal Position and Emergency
Position flashing

Delay to Open Normal LED on

Emergency voltage or frequency
not within acceptable parameters

Power supply harness unplugged

Limit switch harness unplugged

W timing cycle not complete

Check Engine Start Connections,
Generator Breaker, Generator
output, and Engine Control Switch

Plug in harness

Plug in harness

Check W Timer setting

Annunciation

Possible Cause

Corrective Action

ATS Will Not Transfer To NORMAL

Normal Available LED off

None

Normal Position and Emergency
Position LEDs flashing

Delay to Open Emergency LED on

Normal voltage or frequency not
within acceptable parameters

Power supply harness unplugged

Limit switches harness unplugged

T timing cycle not complete

Check utility and utility breakers

Plug in harness

Plug in harness

Check T Timer setting

Troubleshooting

Before beginning any troubleshooting activity, refer to the information package supplied with

the transfer switch and review the description and operation of all accessories supplied. Also

refer to the Installation section of this manual.

Annunciation

Possible Cause

Corrective Action

Engine Does Not START

Emergency Available LED off

Engine start wires not
terminated properly

Generator in “OFF” position

Check Engine Start Connections

Investigate why Engine Control
Switch was turned off