1 standard features 2-2 operating instructions, Power break® ii switches, 1 standard features – GE Industrial Solutions Power Break II Switches, 800-4000A Frames, 240-600Vac User Manual

Page 12: 2 operating instructions, Chapter 2. operation

Advertising
background image

Power Break® II Switches

Chapter 2. Operation

2-1 Standard Features

Power Break II switches are equipped with the following

standard features. The letters are keyed to the switch

photographs in Figures 6 and 7.

A Indicator:

ON

– Red

OFF

– Green

B Indicator:

CHARGED

– Yellow

DISCHARGED

– White

C

ON

button

D

OFF

button

E Manual charging handle
F Integral 36-point terminal block (12 auxiliary

switches, A-B type), Block “A”

G Integral 36-point terminal block (all other con-

nections), Block “B”

H Sealable hinged cover
I Cover mounting screws (4)
K Control Unit interchangeable rating plug
L Test set connection port
M Standard padlock provision
N Dust-resistant ventilation slots

4

Figure 6. Front of the switch, showing the locations of

standard features.

Figure 7. Front of the switch, with the Control unit and top

cover removed.

2-2 Operating Instructions

Sequence of Operations

The sequence of operations that may be performed on the
switch are listed in Table 3. Refer to Chapter 3 for

information about accessory operation.

Operating Instructions for Manually

Operated Switch

Charging the Mechanism Springs

Pull the operating handle down about 90° (until it stops).
Repeat five more times to fully charge the springs.

This

will not close the switch contacts.

The charge indicator

will show

CHARGED

on a yellow background. When the

springs are fully charged, the handle locks in the stored

position.

NOTE:

The switch cannot be closed unless the springs

are fully charged and the handle is stored fully in.

NOTE:

La fermeture de l'interrupteurne peut être réal-

isée à moins que les ressorts soient réarmés tout à fait, et

le levier est complètement remis à la position

d’emmagasinage.