Power Break® II Switches

Chapter 2 – Operation

5

On/Off

Indicator

Charge

Indicator

Main Switch

Contacts

Condition of

Charging Springs

Next Permissible Operating Function

OFF DISCHARGED

Open

Discharged

Mechanism may be charged

OFF CHARGED

Open

Charged

Contacts may be closed

ON DISCHARGED

Closed

Discharged

Mechanism may be recharged or
Contacts may be opened

ON CHARGED

Closed

Charged

Contacts may be opened

Table 3. Sequence of operations that may be performed with Power Break II switches.

Closing the Switch

Close the switch contacts with either of the following
methods:

• Depress

the

ON

button on the front of the switch.

• Energize the (optional) Remote Close accessory by

applying rated voltage to terminals 16 and 34 on

terminal block B.

CAUTION:

The main switch contacts cannot be closed if

the switch latch is held in the tripped position by any of

the following conditions:
• The Bell Alarm with Lockout was not reset after a

ground fault lockout.

• The Undervoltage Release is not energized.
• The Shunt Trip with Lockout is energized.
These conditions must be corrected before the switch

can be closed.

ATTENTION:

Les contacts de l'interrupteur

principal

peuvent être fermés où le loquet de l'interrupteur

est

maintenu en position déclenchée à cause de toute des

conditions suivantes:
• Si la réarmeture du déclencheur n’est pas réalisée

après le verrouillage en position “ouvert” provenant

du courant de surcharge.

• Si le minimum de tension (UVR) n’est pas sous

tension.

• Le déclenchement shunt avec blocage est actionné.
Ces conditions doivent être corrigées avant l'interrupteur

peut être fermé.

CAUTION:

If the switch latch is held in the tripped

position by any of the following conditions and an

attempt is made to close the main switch contacts, the

mechanism will “crash” (the closing springs discharge

with no motion of the switch contact arms). The switch

has been designed and tested to withstand more than

100 crash operations, but repeated attempts to close a

locked-out switch will damage the switch mechanism.
• The Key interlock or padlock is in the locked

OFF

condition.

• The draw-out interlock is engaged with the carriage

between the

TEST

and

T

CONNECTED

positions.

• The walking beam interlock or mechanical interlock

is activated.

ATTENTION:

Si le cliquet de l'interrupteur

est tenu en

position de déclenchement dans n’importe quelle des

conditions suivantes et que l’on tente de fermer les

contacts de l'interrupteur

principal, le mécanisme subira

un “crash” (les ressorts de fermeture se détendent sans

que les bras des contacts du disjoncteur ne bougent).

L'interrupteur a été conçu et testé pour résister à plus de

100 opérations de type “crash,” cependant des tentatives

répétées ayant pour but de fermer un interrupteur

bloqué endommageront le mécanisme de l'interrupteur.

• Si le verrou de clé ou le cadenas est verrouillé en

position

OFF

.

• Si le chariot du verrou débrochable est localisé entre

les positions

TEST

et

CONNECTED

.

L’enclenchement par support mobile ou

enclenchement mécanique est activé.