11 mechanical counter 3-12 auxiliary switch module, Operation, Mechanical counter – GE Industrial Solutions Power Break II Switches, 800-4000A Frames, 240-600Vac User Manual
Page 22: Auxiliary switch module with 12 switches, Auxiliary, Switch wiring diagram, Auxiliary switch module catalog numbers, Power break® ii switches, 11 mechanical counter, 12 auxiliary switch module
Power Break® II Switches
Chapter 3. Accessory Operation
3-11 Mechanical Counter
The Mechanical Counter, shown in Figure 21, counts the
number of times the switch is closed. The catalog number
of the Mechanical Counter is SPCOUNTER. For
installation instructions see GEH-6280.
14
Figure 21. Mechanical Counter.
3-12 Auxiliary Switch Module
The Auxiliary Switch Module, shown in Figure 22,
provides remote indication of the switch main contact
position through the terminals on the terminal block on
the left side of the switch.
Auxiliary Switch Modules are available with 4, 8, and 12
switches with ratings of 6 A at 240 Vac or 600 Vac. Addi-
tional ratings of 0.5 A at 125 Vdc and 0.25 A at 250 Vdc
apply to all models. Catalog numbers are listed in Table
17. For installation instructions see GEH-6274.
Operation
Each auxiliary switch provides two outputs that can be
used to indicate switch main contact position. The A
output is open or closed the same as the switch, while the
B output is the opposite to the switch contacts. Figure 23 is
a wiring diagram of each auxiliary switch.
The connections for the auxiliary switch outputs are
found on the terminal block on the left side of the switch
and are listed in Table 18.
Figure 22. Auxiliary Switch Module with 12 switches.
# Switches
240 Vac
600 Vac
4 SPAS240AB4
SPAS600AB4
8 SPAS240AB8
SPAS600AB8
12 SPAS240AB12
SPAS600AB12
600 Vac devices are not UL listed.
Table 17. Auxiliary Switch Module catalog numbers.
Figure 23. Auxiliary switch wiring diagram.