11 mechanical counter 3-12 auxiliary switch module, Operation, Mechanical counter – GE Industrial Solutions Power Break II Switches, 800-4000A Frames, 240-600Vac User Manual

Page 22: Auxiliary switch module with 12 switches, Auxiliary, Switch wiring diagram, Auxiliary switch module catalog numbers, Power break® ii switches, 11 mechanical counter, 12 auxiliary switch module

Advertising
background image

Power Break® II Switches

Chapter 3. Accessory Operation

3-11 Mechanical Counter

The Mechanical Counter, shown in Figure 21, counts the

number of times the switch is closed. The catalog number

of the Mechanical Counter is SPCOUNTER. For

installation instructions see GEH-6280.

14

Figure 21. Mechanical Counter.

3-12 Auxiliary Switch Module

The Auxiliary Switch Module, shown in Figure 22,

provides remote indication of the switch main contact

position through the terminals on the terminal block on

the left side of the switch.
Auxiliary Switch Modules are available with 4, 8, and 12
switches with ratings of 6 A at 240 Vac or 600 Vac. Addi-

tional ratings of 0.5 A at 125 Vdc and 0.25 A at 250 Vdc

apply to all models. Catalog numbers are listed in Table

17. For installation instructions see GEH-6274.

Operation

Each auxiliary switch provides two outputs that can be
used to indicate switch main contact position. The A

output is open or closed the same as the switch, while the

B output is the opposite to the switch contacts. Figure 23 is

a wiring diagram of each auxiliary switch.
The connections for the auxiliary switch outputs are
found on the terminal block on the left side of the switch

and are listed in Table 18.

Figure 22. Auxiliary Switch Module with 12 switches.

# Switches

240 Vac

600 Vac

4 SPAS240AB4

SPAS600AB4

8 SPAS240AB8

SPAS600AB8

12 SPAS240AB12

SPAS600AB12

600 Vac devices are not UL listed.

Table 17. Auxiliary Switch Module catalog numbers.

Figure 23. Auxiliary switch wiring diagram.

Advertising