Power break® ii switches, Chapter 2. operation, Padlock operation – GE Industrial Solutions Power Break II Switches, 800-4000A Frames, 240-600Vac User Manual

Page 14: Periodic operational checks

Advertising
background image

Power Break® II Switches

Chapter 2. Operation

Opening the Switch

Open the switch contacts with either of the following
methods:

• Depress

the

OFF

button on the front of the switch.

• Energize the (optional) Shunt Trip or Shunt Trip

with Lockout accessory or de-energize the (optional)

Undervoltage Release accessory.

Additional Instructions for Motor-Operated

Switches

Charging the Mechanism Springs

The mechanism closing springs may also be charged by
the following method:

• Short terminals 17 and 35 on the right terminal

block, with a push button or similar device, for a

minimum of five seconds.

• If power is lost during the charge cycle, finish

charging the springs by cycling the charging handle

until the indicator shows

CHARGED

on a yellow

background. When the springs are fully charged, the

handle locks in the stored position.

Automatic Operation

Connect terminals 17 and 35 on the terminal block on the
right side of the switch with a jumper wire. The Motor

Operator will automatically recharge the switch closing

springs whenever the switch closes.

CAUTION:

Do not wire switches for automatic close.

6

ATTENTION:

Ne pas câbler les interrupteurs pour la

fermeture automatique.

Padlock Operation

The padlock prevents the switch from closing by holding
the trip latch in the tripped position. To install the

padlock, use the following procedure:
1. Trip the switch (press the

OFF

button).

2. Grasp the padlock tab (see Figure 6) and pull it out

until it is fully extended, as illustrated in Figure 8.

Note that if the switch contacts are closed, the

padlock tab will not extend.

3. Insert the padlock; the switch will not close.
As many as three

1

/

4

" to

3

/

8

" padlocks may be attached at

one time.

Figure 8. Side view of the switch, showing the padlock tab

extended.

Periodic Operational Checks

Approximately once a year, verify that the switch is
operating correctly by opening and closing the

mechanism.

Wiring Notes

Figure 9 illustrates the terminal block installed on the
right side of the switch. Table 4 lists the device con-

nections to the terminal block. Each terminal point will

accept the following connections:

• Bare stripped wire – one #12 AWG or two #14 AWG.
• Ring or spade connectors – two per terminal.

The terminal screws should be tightened to 7–9 in-lb

torque.
The left terminal block is blank unless the optional
Auxiliary Switch Module accessory is ordered. See Table

16 for the device connections to the Auxiliary Switch

Module terminal block.

Advertising