3–6 shunt trip with lockout, Operation, 6 undervoltage release – GE Industrial Solutions Power Break II Switches, 800-4000A Frames, 240-600Vac User Manual

Page 19: Shunt, Trip, With lockout module, Undervoltage, Release module, Power break® ii switches, 7 undervoltage release

Advertising
background image

Power Break® II Switches

Chapter 3. Accessory Operation

3–6 Shunt Trip with Lockout

The Shunt Trip with Lockout module, shown in Figure

16, allows the switch to be opened electrically from a

remote location and prevents the switch from closing

while the accessory is energized.

Figure 16. Shunt Trip with Lockout module.

If the switch is equipped with a Power+™ Control Unit, it
is configured so that only ground fault trips will activate a

Bell Alarm–Alarm Only or Bell Alarm with Lockout.
The catalog numbers for the Shunt Trip for various

voltage applications are listed in Table 12. For installation

instructions see GEH–6284 or GEH–6519.

Catalog

Number

Voltage

Rating

Peak Inrush

Current, A

Nominal RMS

Current, mA

11

SPSTL012 12

Vdc

19

300

SPSTL024

24 Vac
24 Vdc

15 300

SPSTL048

48 Vac
48 Vdc

7.5 200

SPSTL120

120 Vac
125 Vdc

3.0 80

SPSTL208 208

Vac

1.9

60

SPSTL240

240 Vac
250 Vdc

1.5 45

SPSTL480

480

Vac

0.75

20

SPSTL600

600

Vac

0.60

16

24–600 Vac devices are rated for 50/60 Hz.

Peak inrush current is present for 2–6 ms after activation. This number is

provided so that fuses and supplies can be chosen appropriately.

Ratings for 480 Vac and 600 Vac devices are at the input of the upstream

transformer, included with the accessory and specified in GEH–6519,
which powers the device. For voltage and current ratings at the switch
terminal block, see SPSTL120.

Table 12. Catalog numbers and voltages for the Shunt Trip

with Lockout.

Operation

Apply control voltages to terminals 31 and 32 of the

terminal strip on the right side of the switch to open the

switch. The Shunt Trip with Lockout will cause the switch

to open when the control voltage is greater than 75% of

the dc-rated value or 55% of the ac-rated value.

3-7 Undervoltage Release

The Undervoltage Release (UVR) module, shown in

Figure 17, opens the switch when the input control voltage

drops to 35–60% of its rated value and prevents an open

switch from closing until the input control voltage is

greater than 80% of the rated value.
If the switch is equipped with a Power+™ Control Unit, it
is configured so that only ground fault trips will activate a

Bell Alarm–Alarm Only or Bell Alarm with Lockout.

Figure 17. Undervoltage Release module.

The catalog numbers for the UVR for various voltage
applications are listed in Table 13. For installation

instructions see GEH-6285 or GEH–6520.

Operation

Apply control voltage to terminals 29 and 30 of the
terminal strip on the right side of the switch. When the

applied control voltage is above 80% of the UVR’s rated

value, the switch can be closed. When the voltage drops to

35–60% of the rated value, the UVR will open the switch.

Advertising