Operation, 5 shunt trip, Bell alarm with lockout module – GE Industrial Solutions Power Break II Switches, 800-4000A Frames, 240-600Vac User Manual
Page 18: Shunt, Trip module, Bell alarm with lockout catalog numbers, Catalog numbers and voltages for the shunt trip, Power break® ii switches, Chapter 3. accessory operation
Power Break® II Switches
Chapter 3. Accessory Operation
Figure 13. Bell Alarm with Lockout module.
Catalog No.
Contact Rating
10
SPBAL240
6 A at 240 Vac
0.25 A at 250 Vdc
0.50 A at 125 Vdc
SPBAL600
6 A at 600 Vac
0.25 A at 250 Vdc
0.50 A at 125 Vdc
The 600 V version is not UL listed.
Table 10. Bell Alarm with Lockout catalog numbers.
Operation
The Bell Alarm with Lockout prevents reclosing of the
switch after a ground fault trip until the reset button on
the front of the module is pressed. This trip can be caused
by a ground fault condition detected by the Control Unit.
In addition, the Bell Alarm with Lockout provides
normally open (NO) and normally closed (NC) alarm
outputs available at the terminal block on the right side of
the switch, as illustrated in Figure 14. These outputs are
returned to their normal state when the Bell Alarm with
Lockout reset button is firmly pressed.
Figure 14. Bell Alarm with Lockout connections on the right
terminal block. The contacts are shown in the reset state.
3-5 Shunt Trip
The Shunt Trip module, shown in Figure 15, allows the
switch to be tripped electrically from a remote location.
Figure 15. Shunt Trip module.
If the switch is equipped with a Power+™ Control Unit, it
is configured so that only ground fault trips will activate a
Bell Alarm–Alarm Only or Bell Alarm with Lockout.
The catalog numbers for the Shunt Trip for various
voltage applications are listed in Table 11. For installation
instructions see GEH–6284 or GEH–6519.
Catalog
Number
Voltage
Rating
Peak Inrush
Current, A
Nominal RMS
Current, mA
SPST012 12
Vdc
3.0
200
SPST024
24 Vac
24 Vdc
1.5 140
SPST048
48 Vac
48 Vdc
1.5 110
SPST120
120 Vac
125 Vdc
1.5 85
SPST208 208
Vac
1.5
50
SPST240
240 Vac
250 Vdc
1.5 40
SPST480
480
Vac
0.375
21
SPST600
600
Vac
0.3
17
24–600 Vac devices are rated for 50/60 Hz.
Peak inrush current is present for 2–6 ms after activation. This number is
provided so that fuses and supplies can be chosen appropriately.
Ratings for 480 Vac and 600 Vac devices are at the input of the upstream
transformer, included with the accessory and specified in GEH–6519,
which powers the device. For voltage and current ratings at the switch
terminal block, see SPST120.
Table 11. Catalog numbers and voltages for the Shunt Trip.
Operation
Apply control voltage to terminals 31 and 32 of the
terminal strip on the right side of the switch to open the
switch. The Shunt Trip will cause the switch to open when
the control voltage is greater than 75% of the dc-rated
value or 55% of the ac-rated value.