Operation, 5 shunt trip, Bell alarm with lockout module – GE Industrial Solutions Power Break II Switches, 800-4000A Frames, 240-600Vac User Manual

Page 18: Shunt, Trip module, Bell alarm with lockout catalog numbers, Catalog numbers and voltages for the shunt trip, Power break® ii switches, Chapter 3. accessory operation

Advertising
background image

Power Break® II Switches

Chapter 3. Accessory Operation

Figure 13. Bell Alarm with Lockout module.

Catalog No.

Contact Rating

10

SPBAL240

6 A at 240 Vac

0.25 A at 250 Vdc
0.50 A at 125 Vdc

SPBAL600

6 A at 600 Vac

0.25 A at 250 Vdc
0.50 A at 125 Vdc

The 600 V version is not UL listed.

Table 10. Bell Alarm with Lockout catalog numbers.

Operation

The Bell Alarm with Lockout prevents reclosing of the

switch after a ground fault trip until the reset button on

the front of the module is pressed. This trip can be caused

by a ground fault condition detected by the Control Unit.
In addition, the Bell Alarm with Lockout provides
normally open (NO) and normally closed (NC) alarm

outputs available at the terminal block on the right side of

the switch, as illustrated in Figure 14. These outputs are

returned to their normal state when the Bell Alarm with

Lockout reset button is firmly pressed.

Figure 14. Bell Alarm with Lockout connections on the right

terminal block. The contacts are shown in the reset state.

3-5 Shunt Trip

The Shunt Trip module, shown in Figure 15, allows the

switch to be tripped electrically from a remote location.

Figure 15. Shunt Trip module.

If the switch is equipped with a Power+™ Control Unit, it
is configured so that only ground fault trips will activate a

Bell Alarm–Alarm Only or Bell Alarm with Lockout.
The catalog numbers for the Shunt Trip for various

voltage applications are listed in Table 11. For installation

instructions see GEH–6284 or GEH–6519.

Catalog

Number

Voltage

Rating

Peak Inrush

Current, A

Nominal RMS

Current, mA

SPST012 12

Vdc

3.0

200

SPST024

24 Vac
24 Vdc

1.5 140

SPST048

48 Vac
48 Vdc

1.5 110

SPST120

120 Vac
125 Vdc

1.5 85

SPST208 208

Vac

1.5

50

SPST240

240 Vac
250 Vdc

1.5 40

SPST480

480

Vac

0.375

21

SPST600

600

Vac

0.3

17

24–600 Vac devices are rated for 50/60 Hz.

Peak inrush current is present for 2–6 ms after activation. This number is

provided so that fuses and supplies can be chosen appropriately.

Ratings for 480 Vac and 600 Vac devices are at the input of the upstream

transformer, included with the accessory and specified in GEH–6519,
which powers the device. For voltage and current ratings at the switch
terminal block, see SPST120.

Table 11. Catalog numbers and voltages for the Shunt Trip.

Operation

Apply control voltage to terminals 31 and 32 of the

terminal strip on the right side of the switch to open the

switch. The Shunt Trip will cause the switch to open when

the control voltage is greater than 75% of the dc-rated

value or 55% of the ac-rated value.

Advertising