EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12

Rack Out Legacy or Existing CB

It must be ensured that the supply power to

the compartment is turned off/ compartment is

de-energized for all the incoming and outgoing

circuits of the LVS prior to any work being

conducted on it.

During the installation and related work on the

equipment, it must be ensured that the operator is

using the prescribed PPE for the specified tasks.

Ensure only qualified personnel install, operate, service, and maintain all electrical

equipment.

1. To rack-out legacy (old or original) breaker from compartment, refer to your legacy-breaker’s manual on how

to remove the existing breaker.

Install Secondary Disconnect Bullets (Breaker)

WIRING

Before installing the breaker, the secondary

disconnects must be wired to the EntelliGuard

Breaker.

Wires with wire markers are provided on the

retrofill. Make sure that the switchgear wiring

connection points match up with the original

wiring of the cubicle. This ensures that all wiring

connections are properly made.

Wrong connections will cause the breaker to

malfunction.

This section deals with the installing and wiring the legacy secondary disconnect assemblies on to the Retrofill
EntelliGuard ACB. Installing the secondary-disconnect assembly consists of the following tasks:

• Installation of the secondary disconnect assembly
• Wiring of the secondary disconnect assembly

The Retrofill EntelliGuard ACB has available either of these two options:

• All secondary disconnects installed
• No secondary disconnects installed