EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12

13. As soon as the breaker is resting on the rails, unhook the lift hooks from the ears or holes of the circuit breaker.

Move the hoisting apparatus out of the way.

Figure 22. Retrofill Hoisted and Secured on Rails

14. Push the breaker into the compartment until it can’t be pushed any further in, that is, slide the retrofit cassette

into the compartment until dead-stop.

15. Pull the shutter pad lock lever to defeat the latch on the rail (

Figure 23).

16. Put the rod of 3/8" in the hole of the shutter padlock lever (

Figure 24

).

17. Push the retrofill breaker to “test” position of the legacy breaker. This will be the disconnect position for the

retrofill breaker.

18. Latch the inner rail with outer rail.
19. Remove the rod from the shutter padlock lever and allow the lever to go back.
20. Now the new retrofill breaker can be racked in, using the racking mechanism provided in the breaker.