30

EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 02/12

Figure 23. Latching Inner Rail with Outer Rail

Figure 24. Inserting Rod

21. Remove the racking tool from the storage location on the retrofill front panel and grab the handle.
22. Pull out the torque bar from inside the handle and extend.
23. Take a blade-type screwdriver, insert it in the slot or rack-out lock of the breaker (

Figure 25

), and turn it

clockwise 45°to the right so that the racking handle shutter, inside and behind the racking hole, also moves to
the right. (The insertion slot resembles a vehicle ignition lock.)

Figure 25. Racking in AKD6—Retrofill

24. After turning the screwdriver to the right with the shutter sliding to the right, remove the screwdriver and insert

the racking tool in the handle-insertion hole. It’s located on the left side.

25. Insert this tool so it that grabs or engages the racking mechanism inside the hole.
26. Line up the racking tool or crank with the handle straight up so that you can get some good leverage or

torque. Then, crank clockwise so that the retrofill starts to move in, slowly sliding forward into the
compartment.

27. Rotating clockwise racks the circuit breaker all the way into the enclosure.