Alert Response Address (ARA):

This feature enables the

‘master’ to rapidly determine which ‘slave’ power supply

triggered the SMBAlert signal without having to poll each

power supply one at a time. During normal operation the

power supply activates (pulls down LO) the Alert signal line

indicating that it needs attention when a ‘state’ change

occurs. The master can determine who pulled the ‘alert’ line

by sending out the alert-response-address, address 12b, with

a ‘read’ instruction. If the power supply triggered the ‘alert’ it

should respond back with its address. The instruction takes

the form below;

1

8

1

8

1

8

1

1

S

ARA address

Rd A My address

A

PEC

A

P

If during the ARA response multiple power supplies send out

their addresses, then the actual address received by the

master is the lowest address from the combinations of those

power supplies that responded.

The ‘my address’ field contains the address of the power

supply in the 7 most significant bits (msb) of the byte. The lsb

of the byte is a don’t care, it could be a 0 or a 1. For more

information refer to the SMBus specification.

The µC does not have the ability to listen to the actual

address that is sent over the bus, if multiple ‘slaves’ respond

simultaneously, and therefore it does not clear its SMBAlert

line. The host should read the status of the power supply

whose address was actually sent across the bus. Reading

either the read_status [0 x D0] or status_word [0 x 79] would

clear the SMBALert line of the power supply that was

addressed. The power supply will not re-assert the SMBAlert

line unless the status states actually changed.
If the SMBAlert line is still asserted, the host should send out
an ARA request again and find out who else asserted
SMBAlert. This process needs to continue until the SMBAlert is
released which is a clear indication that all power supplies
that asserted SMBAlert have had their status states read
back.

Dual, redundant buses:

Two independent I

2

C lines provide

true communications bus redundancy and allow two

independent controllers to sequentially control the power

supply. For example, a short or an open connection in one of

the I

2

C lines does not affect communications capability on the

other I

2

C line. Failure of a ‘master’ controller does not affect

the power supplies and the second ‘master’ can take over

control at any time.
Conceptually a Digital Signal Processor (DSP) referenced to

Vout(-) of the power supply provides secondary control. A

Bidirectional Isolator provides the required isolation between

power GRD, Vout(-) and signal GRD (Logic_GRD). A secondary

micro controller provides instructions to and receives

operational data from the DSP. The secondary micro

controller also controls the communications over two

independent I2C lines to two independent system controllers.



The secondary micro controller is designed to default to I2C_0

when powered up. If only a single system controller is utilized,

it should be connected to I2C_0. In this case the I2C_1 line is

totally transparent as if it does not exist.
If two independent system controllers are utilized, then one of

them should be connected to I2C_0 and the other to I2C_1.
At power up the master connected to I2C_0 has control of the

bus. See the section on Dual Master Control for further

description of this feature.

PMBus

TM

Commands

Standard instruction:

Up to two bytes of data may follow an

instruction depending on the required data content. Analog
data is always transmitted as LSB followed by MSB. PEC is
optional and includes the address and data fields.

1

8

1

8

1

S Slave address

Wr A Command Code

A

8

1

8

1

8

1 1

Low data byte

A

High data byte

A

PEC A

P

Master to Slave Slave to Master

SMBUS annotations; S – Start , Wr – Write, Sr – re-Start, Rd

– Read,

A – Acknowledge, NA – not-acknowledged, P – Stop

Standard READ:

Up to two bytes of data may follow a READ

request depending on the required data content. Analog

data is always transmitted as LSB followed by MSB. PEC is
mandatory and includes the address and data fields

.

1

7

1

1

8

1

S

Slave address

Wr

A Command Code

A

1

7

1

1

8

1

Sr Slave Address

Rd

A

LSB

A

8

1

8

1

1

MSB

A

PEC

No-ack

P

Block communications:

When writing or reading more than

two bytes of data at a time BLOCK instructions for WRITE and

READ commands are used instead of the Standard

Instructions above to write or read any number of bytes

greater than two.

µC

DSP

Bidirectional

Isolator

I

2

C_0

I

2

C 1