Status-2, Status-1, Alarm-2 – GE Industrial Solutions CAR2912TE series User Manual

Page 16: Alarm-1, Car2912te series front-end, Preliminary data sheet, Manufacturer-specific pmbus, Commands

Advertising
background image

GE

Preliminary Data Sheet

CAR2912TE series front-end

Input: 90Vac to 264Vac; Output: 12Vdc @ 2900W; 3.3 or 5Vdc @ 4A Standby

October 21, 2013

©2013 General Electric Company. All rights reserved.

Page 16

Manufacturer-Specific PMBus

TM

Commands

Many of the manufacturer-specific commands read back

more than two bytes

.

If more than two bytes of data are

returned, the standard SMBus

TM

Block read is utilized. In this

process, the Master issues a Write command followed by the

data transfer from the power supply. The first byte of the

Block Read data field sends back in hex format the number of

data bytes, exclusive of the PEC number, that follows. Analog

data is always transmitted LSB followed by MSB. A No-ack

following the PEC byte signifies that the transmission is

complete and is being terminated by the ‘host’.

Mfr_Specific Status and alarm registers:

The content and

partitioning of these registers is significantly different than

the standard register set in the PMBus™ specification. More

information is provided by these registers and they are either

accessed rapidly, at once, using the ‘multi parameter’ read

back scheme of this document, or in batches of two STATUS

and two ALARM registers.

Read_status (D0h) :

This ‘manufacturer specific’ command is

the basic read back returning STATUS and ALARM register

data, output voltage, output current, and internal

temperature data in a single read.

1

8

1

8

1

S

Slave address

Wr A Command Code

A

1

8

1

8

1

Sr

Slave address

Rd

A Byte count = 10

A

8

1

8

1

8

1

Status-2

A

Status-1

A

Alarm-2

A

8

1

8

1

8

1

Alarm-1

A Voltage LSB

A

Voltage MSB

A

8

1

8

1

Current LSB

A

Current MSB

A

8

1

8

1

8

1

1

Temperature LSB

A Temperature MSB A PEC NA

P


Read_Status_state (0xD1):

This command returns the

STATUS-2 and STATUS-1 register values using the standard

‘read’ format.

Status-2

Bit

Position

Flag

Default

Value

7

PEC Error

0

6

Will restart

0

5

Invalid_Instruction

0

4

Power_Capacity [HL = 1]

x

3

Isolation test failed

0

2

Restarted_OK

0

1

Data out_of_range

0

0

Remote ON/OFF [logic HI = 1]

x

Isolation test failed: The ‘system controller’ has to determine

that sufficient capacity exists in the system to take a power

supply ‘off line’ in order to test its isolation capability. Since

the power supply cannot determine whether sufficient

redundancy is available, the results of this test are provided,

but the ‘internal fault’ flag is not set.


Status-1

Bit

Position

Flag

Default

Value

7

X

0

6

Isolation_Test_OK

0

5

Internal_Fault

0

4

Shutdown

0

3

Service LED ON

0

2

External_Fault

0

1

LEDs_Test_ON

0

0

Output ON

x


Read_Alarm_state (0xD2):

This command returns the

ALARM-2 and ALARM-1 register values using the standard

‘read’ format.


Alarm-2

Bit

Position

Flag

Default

Value

7

FAN_Fault

0

6

No_Primary

0

5

Primary_OT

0

4

DC/DC_OT

0

3

Vo lower than BUS

0

2

Thermal sensor filed

0

1

Stby_out_of_limits

0

0

Power_Delivery

0


Power Delivery:
The power supply compares its internal

sourced current to the current requested by the current share

pin. If the difference is > 10A, a fault is issued.


Alarm-1

Bit

Position

Flag

Default

Value

7

POWER LIMIT

0

6

PRIMARY Fault

0

5

OT_Shutdown

0

4

OT_Warning

0

3

IN OVERCURRENT

0

2

OV_Shutdown

0

1

VOUT_out_of_limits

0

0

VIN_out_of_limits

0