GE

Preliminary Data Sheet

CAR2912TE series front-end

Input: 90Vac to 264Vac; Output: 12Vdc @ 2900W; 3.3 or 5Vdc @ 4A Standby

October 21, 2013

©2013 General Electric Company. All rights reserved.

Page 12

Command

Hex

Code

Data

Field

Non-

Volatile

Memory

Storage

Read_Vout

0x8B

2

Read_Iout

0x8C

2

Read_temperature_1

0x8D

2

Read_temperature_2

0x8E

2

Read_temperature_3

0x8F

2

Read_fan_speed_1

0x90

2

Read_fan_speed_2

0x91

2

Read_Pin

0x97

2

Mfr_ID

0x99

5

Mfr_model

0x9A

16

Mfr_revision

0x9B

4

Mfr_serial

0x9E

15

Read_status

0xD0

10

Read_Status_state

0xD1

2

Read_Alarm_state

0xD2

2

Read_fan_speed

0XD3

4

Read_input_string

0xD4

2

Read_firmware_rev

0xD5

3

Read_run_timer

0xD6

3

Read Bus Status

0xD7

1

Take over bus control

0xD8

EEPROM Record

0xD9

128

Stretch_LO_25ms

0XDA

0

Test Function

0xDF

1

Compatibility code

0xE0

20

Memory capability

0xE1

5

Boot loader

0xE2

1

Data transfer

0xE3

≤32

Command Descriptions

Operation (0x01) :

By default the Power supply is turned ON

at power up as long as Power ON/OFF signal pin is active HI.

The Operation command is used to turn the Power Supply ON

or OFF via the PMBus. The data byte below follows the

OPERATION command.

FUNCTION

DATA BYTE

Unit ON

80

Unit OFF

00

To RESET the power supply cycle the power supply OFF, wait

at least 2 seconds, and then turn back ON. All alarms and

shutdowns are cleared during a restart.

Clear_faults (0x03):

This command clears all STATUS and

FAULT registers and resets the SMBAlert# line of both the

power supply and I

2

C bus STATUS register.

If a fault, or a STATUS needing attention, still persists after the

issuance of the clear_faults command, the specific registers

indicating the fault are reset and the specific SMBAlert# line is

activated again.

WRITE_PROTECT register (0x10):

Used to control writing to

the PMBus device. The intent of this command is to provide

protection against accidental changes. All supported

command parameters may have their parameters read,

regardless of the write_protect settings. The contents of this

register can be stored to non-volatile memory using the

Store_default_code command. The default setting of this

register is disable_all_writes except write_protect 0x80h.

FUNCTION

DATA BYTE

Enable all writes

00

Disable all writes except write_protect

80

Disable all writes except write_protect and

OPERATION

40

Restore_Default_All (0x12):

Restores all register values and

responses to the default parameters set in the power supply.


Store_default_code (0x13):

Changes the default setting of a

single register. In this fashion some protection is offered to

ensure that only those registers that are desired to be

changed are in fact changed.

Restore_default_code (0x14):

Restore only a specific register

parameter to its default parameter.


Vout_mode (0x20):

This is a ‘read only’ register. The upper

three bits specify the supported data format, in this case

Direct mode. The lower five bits are not used when direct

mode is specified since there are three variables for each

conversion.

Mode

Bits [7:5]

Bits [4:0] (Parameter)

Direct

010b

Set to 00000b

Vout_Command (0x21) :

This command is used to change the

output voltage of the power supply.


Changing the output voltage should be performed

simultaneously to all power supplies operating in parallel

using the Global Address (Broadcast) feature. If only a single

power supply is instructed to change its output, it may

attempt to source all the required power which can cause

either a power limit or shutdown condition.

Software programming of output voltage permanently

overrides the set point voltage configured by the Vprog signal

pin. The program no longer looks at the ‘Vprog pin’ and will

not respond to any hardware voltage settings. If power is

removed from the µController it will reset itself into its default

Advertising