GE

Preliminary Data Sheet

CAR2912TE series front-end

Input: 90Vac to 264Vac; Output: 12Vdc @ 2900W; 3.3 or 5Vdc @ 4A Standby

October 21, 2013

©2013 General Electric Company. All rights reserved.

Page 14

Iout_OC_fault_limit (0x46):

Sets the value at which the power

supply will shut down. The default OC_fault_limit is 68Adc at

high_line and 30A at low_line. (The value is contingent on

whether the power supply operates in the low_line or

high_line mode). This level can be permanently changed and

stored in non-volatile memory. Which level is changed is

contingent on the input voltage applied to the power supply

at the time the change takes place.

Iout_OC_fault_response (0x47):

Sets the response if the

output overload exceeds the OC_Fault_limit value. The

default OC_fault_response is hiccup (0xF8). The only two

allowable states are latched (0xC0) or hiccup. The default

response state can be permanently changed and stored in

non-volatile memory. The response is the same for both

low_line and high_line operations.

Iout_OC_warn_limit (0x4A):

Sets the value at which the

power supply issues a warning that the output current is

getting too close to the shutdown level. The default

OC_Warn_limit is set to 64.8A at high_line and 27.8A at

low_line. This level can be permanently changed and stored

in non-volatile memory. Which level is changed is contingent

on the input voltage applied to the power supply at the time

the change takes place.

OT_fault_limit (0x4F ):

Sets the temperature value at which

the power supply shuts down. The default OT_fault_limit is

set at TBD°C. This level can be permanently changed and

stored in non-volatile memory.

OT_fault_response (0x50):

Sets the response if the output

overtemperature exceeds the OT_Fault_limit value. The

default OT_fault_response is hiccup (0xC0). The only two

allowable states are latched (0x80) or hiccup. The default

response state can be permanently changed and stored in

non-volatile memory.


OT_warn_limit (0x51):

Sets the value at which the power

supply issues a warning that internal temperatures are

getting too close to the shutdown level. The default

OT_Warn_limit is set to TBD°C. This level can be permanently

changed and stored in non-volatile memory.


Vin_OV_fault_limit (0x55):

Sets the value at which the power

supply shuts down because the input voltage exceeds the

allowable operational limit. The default Vin_OV_fault_limit is

set at 300Vac. This level can be permanently lowered and

stored in non-volatile memory.


Vin_OV_fault_response (0x56):

Sets the response if the input

voltage level exceeds the Vin_OV_fault_limit value. The

default Vin_OV_fault_response is restart (0xC0). The only two

allowable states are latched (0x80) and restart (0xC0). The

default response state can be permanently changed and

stored in non-volatile memory.

Vin_UV_warn_limit (0x58):

This is another warning flag

indicating that the input voltage is decreasing dangerously

close to the low input voltage shutdown level. The default

UV_fault_limit is 90Vac. This level can be permanently raised,

but not lowered, and stored in non-volatile memory.


Vin_UV_fault_limit (0x59):

Sets the value at which the power

supply shuts down because the input voltage falls below the

allowable operational limit. The default Vin_UV_fault_limit is

set at 85Vac. This level can be permanently raised and stored

in non-volatile memory

Vin_UV_fault_response (0x5A):

Sets the response if the input

voltage level falls below the Vin_UV_fault_limit value. The

default Vin_UV_fault_response is restart (0xC0). The only two

allowable states are latched (0x80) and restart (0xC0). The

default response state can be permanently changed and

stored in non-volatile memory.

STATUS_BYTE (0x78) :

Returns one byte of information with a

summary of the most critical device faults.

Bit

Position

Flag

Default

Value

7

X

0

6

OFF

0

5

VOUT Overvoltage

0

4

IOUT Overcurrent

0

3

VIN Undervoltage

0

2

Temperature

0

1

CML (Comm. Memory Fault)

0

0

None of the above

0

STATUS_WORD (0x79):

Returns status_byte as the low byte

and the following high_byte.

Bit

Position

Flag

Default

Value

7

VOUT fault or warning

0

6

IOUT fault or warning

0

5

INPUT

0

4

MFR SPECIFIC

0

3

nPOWER_GOOD

0

2

FANS

0

1

OTHER

0

0

UNKNOWN

0