Car2912te series front-end, Preliminary data sheet, Read back descriptions – GE Industrial Solutions CAR2912TE series User Manual

Page 15

Advertising
background image

GE

Preliminary Data Sheet

CAR2912TE series front-end

Input: 90Vac to 264Vac; Output: 12Vdc @ 2900W; 3.3 or 5Vdc @ 4A Standby

October 21, 2013

©2013 General Electric Company. All rights reserved.

Page 15

STATUS_VOUT (0X7A):

Returns one byte of information of

output voltage related faults.

Bit

Position

Flag

Default

Value

7

VOUT OV Fault

0

6

VOUT_OV_WARNING

0

5

VOUT_UV_WARNING

0

4

VOUT UV Fault

0

3 - 0

X

0

STATUS_IOUT (0X7B):

Returns one byte of information of

output current related faults.

Bit

Position

Flag

Default

Value

7

IOUT OC Fault

0

6

X

0

5

IOUT OC Warning

0

4

X

0

3

CURRENT SHARE FAULT

0

2

IN POWER LIMITING MODE

0

1 - 0

X

0

STATUS_INPUT (0X7C):

Returns one byte of information of

input voltage related faults.

Bit

Position

Flag

Default

Value

7

VIN_OV_Fault

0

6

VIN_OV_Warning

0

5

VIN_UV_ Warning

0

4

VIN_UV_Fault

0

3

Unit OFF for low input voltage

0

2

IIN_OC_Fault

0

1 - 0

X

0

STATUS_TEMPERATURE (0x7D):

Returns one byte of

information of temperature related faults.

Bit

Position

Flag

Default

Value

7

OT Fault

0

6

OT Warning

0

5 - 0

X

0

STATUS_CML (0X7E):

Returns one byte of information of

communication related faults.

Bit

Position

Flag

Default

Value

7

Invalid/Unsupported Command

0

6

Invalid/Unsupported Data

0

5

Packet Error Check Failed

0

4 - 2

X

0

1

Other Communication Fault

0

0

X

0

Read back Descriptions

Single parameter read back:

Functions can be read back one

at a time using the read_word_protocol with PEC. A

command is first sent out notifying the slave what function is

to be read back followed by the data transfer.
Analog data is always transmitted LSB followed by MSB. A NA

following the PEC byte signifies that the transmission is

complete and is being terminated by the ‘host’.

1

8

1

8

1

S Slave address

Wr A Command Code

A

1

8

1

Sr Slave address

Rd

A

8

1

8

1

8

1

1

LSB

A

MSB

A

PEC NA

P


Read_fan_speed 1 & 2 (0x90, 0x91):

Reading the fan speed is

in Direct Mode returning the RPM value of the fan.

Read_FRU_ID (0x99,0x9A,0x9B,0x9E):

Returns FRU

information. Must be executed one register at a time.

1

8

1

8

1

S

Slave address

Wr A

Command 0x9x

A

1

8

1

8

1

Sr

Slave address

Rd

A

Byte count = x

A

8

1

8

1

8

1

8

1

1

Byte_1

A Byte A

Byte_x

A PEC NA P


Mfr_ID (0x99):

Manufacturer in ASCII – 5 characters

maximum,

General Electric – Critical Power represented as,

GE-CP

Mfr_ID (0x9A):

Manufacturer model-number in ASCII – 16

characters, for this unit: CAR2912TEBXXZ01A

Mfr-revision (0x9B):

Total 4 bytes

Each byte is partitioned into high and low nibbles

Example: FF is read as 16.16

00 is read as 1.1

Series

Hardware Rev

Primary µC

Secondary µC

Mfr_serial (0x9E):

Product serial number includes the

manufacturing date, manufacturing location in up to 15

characters. For example:

13KZ51018193xxx, is decoded as;

13 – year of manufacture, 2013

KZ – manufacturing location, in this case Matamoros

51 – week of manufacture

018193xxx – serial #, mfr choice