GE Industrial Solutions A-Series II Panelboards THQB User Manual

Page 2

Advertising
background image

DEH40158

DEH40158 Rev.No.01

2

should be clamped with main bus using screws [4] with a maximum of 60 in-lb
torque.




Figure 1. Installation of a THQB circuit breaker kit on interior, catalog number
ASPP6QB6D, into an A-Series

®

II Panelboards.


5. Place the breaker as shown in fig.1 such that breaker strap hole aligns with

breaker mounting strap tapped hole and other end of breaker snaps with 3X base
lancing slot provided and then tighten terminal screws completely with 27-36 in-
lb.

6. Remove the eight screws [6] of existing one filler plates from dead front where

THQB breaker needs to be installed, as illustrated in Figure 2.

Advertising