GE Industrial Solutions Power-Vac ML-20 Mechanism User Manual

Page 11

Advertising
background image

11

SECTION 8—Dimensional Checks

With the breaker closed and the gag plate installed, perform

the following dimensional checks.

8.1—Primary Contact Erosion

In the closed position, the erosion marker (1, Figure 6) below

the bus bar is aligned with a reference mark on the

interrupter’s movable stem. As contact erosion occurs, the

erosion mark will move upward away from the erosion

pointer. When the seribed band on the interrupter’s movable
stem is completely above the top surface of the pointer, 1/8

inch erosion has occurred and the interrupter should be

replaced.

8.2—ML-20 Wipe Spring Compression

With the breaker closed and the closing spring gagged,

measure with a feeler gauge and record the distance between

the bellville washer and the trunion between the bell crank

arms.

8.3—Contact Gap

The method of measuring the contact gap is as follows: With

the breaker in the open position, the closing springs charged,

and the closing spring gag plate installed, apply a piece of

masking tape to the surface of the operating rod insulator as
shown in Figure 7. Using a reference block, make a mark on

the tape near the top on all three poles. It is also advisable to

put a reference mark on the tape to identify to which pole the

tape is applied. Remove the closing spring gag plate and close

the breaker. Using the same procedure as above, re-mark the
tape. This new mark will be near the bottom of the tape. Trip

the breaker, remove the tapes and re-apply them to a flat

surface. Measure the distance between the two lines.

A caliper will give an accurate reading of the contact gap,


Dimension G: The gaps must be between the 0.655 inch

maximum at the center pole and 0.595 inch minimum at the

outer poles. It is not necessary that all readings correspond. A

typically adjusted breaker will have more gap and wipe on the

center pole than on the outside poles.


The close coil and trip coil plunger gap dimensional checks are

made in the operating mechanism which is accessible from

the bottom. To accommodate these checks, the breaker

should be turned on its right side resting on two-by-four wood

blocks. DO NOT use the portable breaker lift truck.


CAUTION: DO NOT ALLOW ANYTHING TO COME IN

CONTACT WITH THE INTERLOCK ROLLER (4, Fig. 18) ON
THE RIGHT SIDE OF THE MECHANISM.

Figure 7 Contact gap

Advertising