1—ordering instructions, 1—general, 2—wipe adjustment – GE Industrial Solutions Power-Vac ML-20 Mechanism User Manual

Page 23: 3—contact gap adjustment, 4—trip coil plunger

Advertising
background image

23

SECTION 15—Renewal Parts

It is recommended that sufficient renewal parts be carried in

stock to enable the prompt replacement of any worn, broken

or damaged parts. A stock of such parts minimizes service

interruptions caused by breakdowns, and saves time and

expense. When continuous operation is a primary
consideration, more renewal parts should be carried, the

amount depending upon the severity of the service and the

time required to secure replacements.

Renewal parts which are furnished may not be identical to the

original parts, but they will be interchangeable.

Renewal Part numbers are available from your local GE Sales

office.

15.1—Ordering Instructions

1. Always specify the complete nameplate data of both the

breaker and mechanism.

2. Specify the quantity, catalog number (if listed), reference

number (if listed), and description of each part ordered,
and the parts bulletin number.

3. Standard hardware, such as screws, bolts, nuts, washer,

etc., should be purchased locally.

SECTION 16—Mechanical Adjustments

16.1—General

The ML-20 Mechanism has been designed for extended

intervals between maintenance. In most cases only the wipe

and gap adjustments will require re-setting throughout the life

of the circuit breaker.

16.2—Wipe Adjustment

Wipe is the additional compression of a preloaded spring,

used to apply force to the vacuum interrupter contacts and

to provide opening kick-off force.

The contact wipe adjustment should always be made before

making the contact gap adjustment.

ML-20 The wipe measurement is made with the breaker

closed and the closing spring gagged. Measure with a feeler
gauge the distance between the bellville washer and the

trunion between the bell cranks arms. Adjustment is not

required if wipe is more than 0.100 inch. After adjustment the

wipe should be 0.160 – 0.185 inch.

To adjust the primary contact wipe, close the breaker and
proceed as follows:

1. Loosen, but do not remove, the two capscrews (9, Figure

8) holding the interrupter clamp.

2. Check that the interrupter clamp is loose. A light pry at

the clamp half-junction may be required to loosen the
wedging action of the clamp.

3. Hold the hexagon projection (6, Figure 6) at the bottom

of the operating rod insulator (1 inch wrench) and loosen
the adjacent locknut (3/4 inch wrench). (Refer to 4,

Figure 6). Adjust by rotating the operating rod insulator.

The thread is 1/2-13 and each turn will give about 0.076

inch change in primary wipe. Screw the operating rod

insulator toward the interrupter to increase wipe.

4. After setting the contact wipe on each phase, torque the

operating rod locknut (4, Figure 6) to 40-50 pounds/foot

while holding the hex projection (6) to prevent the
operating rod insulator (7) from turning. Tighten the

clamp screws (9) to 8-10 pounds/foot and trip the breaker

open. This procedure prevents accidental twisting of the

interrupter’s operating rod by loading the contacts with

the wipe springs and forcing relative rotation to occur at
the clamp interface.

After adjustment, remeasure the wipe dimensions. If the wipe

settings are within the required limits, there is an adequate

contact closing relationship between the poles.

16.3—Contact Gap Adjustment

The gap adjustment refers to the separation, or gap, between

the primary contacts within the vacuum interrupter. Before

attempting to measure or set the gap adjustment, verify that

the wipe settings are within acceptable limits. Any change of
the wipe settings will affect the gap settings.

1. Adjust the center phases first. The contact gap must be

0.595 – 0.655. The adjustment of the outer phases
affects the center phase measurement. With the breaker

in the open position and the closing spring discharged,

locate the gap adjusting nuts on the opening spring rods

connected to the outer phase bell cranks (Figure 12).

Loosen the jam nut on both rods. Back off the adjusting

bolt on the center phase VI stop (Figure 12).

2. Advance or retard the adjusting nuts depending on which

way you want to change the gap. Move both nuts the
same amount.

3. Lock the jam nuts after setting the adjusting nuts.

Operate the breaker a few times and remeasure the gap
following the procedure described in DIMENSIONAL

CHECKS, item 3.

4. Readjust the center phase VI stop (Figure 12). Set

adjusting screw for no clearance between stop and wipe

spring rod striker with the breaker open.

After adjustment of the left and right phase, remeasure the

center phase. The center phase should not exceed 0.655 inch.
If it does then readjust the left and right phases.

16.4—Trip Coil Plunger

To adjust trip coil plunger gap (Figure 9), lift locktab away

from adjusting nut. Turn adjusting nut until trip pin makes
contact with trip arm while maintaining dimension T. Bend

locktab to secure adjusting nut.

Advertising