Figure 11 sample operating speed graphs – GE Industrial Solutions Power-Vac ML-20 Mechanism User Manual

Page 19

Advertising
background image

19

SECTION 12—Timing

Timing and speed checks are optional and also depend on the

level of maintenance performed. Generally these tests are not

required for normal maintenance. If a new mechanism has

been installed or extensive repair, replacement or major
disassembly has been performed, it is recommended that

these tests be performed.

To determine contact velocity, a travel recorder and or an

oscillograph are required. Optional, travel recorder linkage can
be obtained through your local GE Sales Office by ordering

part number 0144D1235G002. A typical travel trace and

interpretation are shown in Figure 11.

Timing may be checked by monitoring control circuit voltage

and using no more than six volts DC and one ampere through
the vacuum interrupter contact to indicate closed or open

condition. Typical time ranges vary

with

coil voltage, but

nominal values are:

Initiation of trip signal to contact parting

5 Cycle Breaker 32-45Milliseconds

2 Milliseconds Maximum Pole Spread

Initiation of close signal to contact closing

45-75 Milliseconds (DC Control Voltage)

35-65 Milliseconds (AC Control Voltage)

2 Milliseconds maximum pole spread

Trip-free operation maybe checked by applying a simultaneous

close and trip signal, and a minimum re-close operation may

be checked by tripping a charged breaker open while
maintaining a close signal.

Instantaneous re-close time* 85-140 Milliseconds.

*Time from application of trip signal until breaker contacts

re-close.


Figure 11 Sample operating speed graphs

* For breakers equipped with an opening dashpot,
there is virtually no overtravel or rebound.

Advertising