Powervac, Vacuum circuit breaker, With ml-20 mechanism – GE Industrial Solutions Power-Vac ML-20 Mechanism User Manual

Page 4: 1—safety, 2—maintenance

Advertising
background image

4

PowerVac

®

Vacuum Circuit Breaker

with ML-20 Mechanism

SECTION 1—Introduction

This manual provides the information needed by the user to

properly install, operate and maintain the ML-20 PowerVac

®

Breaker.

The PowerVac

®

vacuum breaker is a horizontal drawout

interrupting element for use in metalclad switchgear to provide
protection and control of electrical apparatus and power systems.

To the extent required applicable ANSI, IEEE and NEMA Standards

are met. No such assurances are given with respect to local

codes and ordinances, as they vary greatly.

1.1—Safety

Each user must maintain a safety program for the protection of

personnel, as well as other equipment, from the potential hazards
associated with electrical equipment.

The following requirements are intended to augment the user's

safety program, but NOT supplant the user's responsibility for
devising a complete safety program. The following basic industry

practiced safety requirements are applicable to all major electrical

equipment such as switchgear or switchboards. GE neither

condones nor assumes any responsibility for practices which

deviate from the following:

1. ALL CONDUCTORS MUST BE ASSUMED TO BE ENERGIZED

UNLESS THEIR POTENTIAL HAS BEEN MEASURED AS

GROUND AND ADEQUATE CAPACITY GROUNDING

ASSEMBLIES HAVE BEEN APPLIED TO PREVENT
ENERGIZING. Many accidents have been caused by

unplanned energization from non-recognized back feeds,

equipment malfunctions, and from a wide variety of sources.


2. It is strongly recommended that all equipment be completely

de-energized, verified to be “dead”, then grounded with

adequate capacity grounding assemblies prior to any

maintenance. The grounding cable assemblies must be able

to withstand energizing fault levels so that protective
equipment may clear the circuit safely. Additional discussion

on this concept is covered in Chapter 20 of ANSI/NFPA 70B,

Electrical Equipment Maintenance.


3. Although interlocks to reduce some of the risks are provided,

the individual's actions while performing service or

maintenance are essential to prevent accidents. Each person's

knowledge; mental awareness; and planned and executed

actions often determine if an accident will occur. The most
important method of avoiding accidents is for all associated

personnel to carefully apply a thorough under-standing of the

specific equipment from the viewpoints of its purpose, its

construction, its operation and the situations which could be
hazardous.

All personnel associated with installation, operation and

maintenance of electrical equipment, such as power circuit
breakers and other power handling equipment, must be

thoroughly instructed, with periodic retraining, regarding power

equipment in general as well as the particular model of

equipment with which they are working.

Instruction books, actual devices and appropriate safety and

maintenance practices such as OSHA publications, National
Electric Safety Code (ANSI C2), National Electric Code, and

National Fire Protection Association (NFPA) 70B Electrical

Equipment Maintenance must be closely studied and followed.

During actual work, supervision should audit practices to assure
conformance.

1.2—Maintenance

Excellent maintenance is essential for reliability and safety of any

electrical equipment. Maintenance programs must be tuned to

the specific application, well planned and carried out consistent

with both industry experience and manufacturer's

recommendations. Local environment must always be considered
in such programs, including such variables as ambient

temperatures, extreme moisture, number of operations, corrosive

atmosphere or major insect problems and any other unusual or

abusive condition of the application. One of the critical service
activities, sometimes neglected, involves the calibration of various

control devices. These monitored conditions in the primary and

secondary circuits, sometimes initiating emergency corrective

action such as opening or closing circuit breakers. In view of the

vital role of these devices, it is important that a periodic test
program be followed. As was outlined above, it is recognized that

the interval between periodic checks will vary depending upon

environment, the type of device and the user's experience.


It is the GE recommendation that, until the user has accumulated

enough experience to select a test interval better suited to the

individual requirements, all significant calibrations be checked at

an interval of one to two years.


To accomplish this, some devices can be adequately tested using

test sets. Specific calibration instructions on particular devices

typically are provided by supplied instruction books.


Instruction books supplied by manufacturers address components

that would normally require service or maintenance during the

useful life of the equipment. However, they can not include every

possible part that could under adverse environments.

Maintenance personnel must be alert to deterioration of any part
of the supplied switchgear, taking actions, as necessary to restore

it to serviceable status.

Industry publications of recommended maintenance practices
such as ANSI/NFPA 70B, Electrical Equipment Maintenance,

should be carefully studied and applied in each user's formation of

planned maintenance.

Some users may require additional assistance from GE in the

planning and performance of maintenance. Local GE Sales can be

contracted to either undertake maintenance or to provide

technical assistance such as the latest publications.

The performance and safety of all equipment may be

compromised by the modification of supplied parts or their

replacement by non-identical substitutes. All such design changes
must be qualified to the original manufacturers specifications.

The user should methodically keep written maintenance records

as an aid in future service planning and equipment reliability

improvement. Unusual experiences should be promptly
communicated to GE.

Advertising