1—general, 1 interrupter, 2 trouble reporting – GE Industrial Solutions Power-Vac ML-20 Mechanism User Manual

Page 17: 2—service conditions, 3—fault interruptions, 5—transfer finger wear, 6—mechanism, 7—primary insulation parts

Advertising
background image

17

SECTION 11—Maintenance


WARNING:
BEFORE ANY MAINTENANCE WORK IS
PERFORMED, MAKE CERTAIN THAT ALL CONTROL

CIRCUITS ARE DE-ENERGIZED AND THAT THE BREAKER IS

REMOVED FROM THE METALCLAD UNIT. DO NOT WORK

ON THE BREAKER OR MECHANISM WHILE IT IS IN THE

CLOSED POSITION WITHOUT TAKING PRE- CAUTIONS TO
PREVENT ACCIDENTAL TRIPPING. DO NOT WORK ON THE

BREAKER WHILE THE CLOSING SPRING IS CHARGED

UNLESS IT IS SECURED IN THAT POSITION BY THE
CLOSING-SPRING GAG.

11.1—General

PowerVac

®

circuit breakers have been designed to be as

maintenance-free as practicable. They include features such

as sealed vacuum interrupters and long-life synthetic greases

which contribute to many years of trouble-free performance

with a minimum amount of maintenance.

11.1.1 Interrupter

The interrupter used in this breaker is a reliable, clean

interrupting element. Since the contacts are contained in a

vacuum chamber, they remain clean and require no

maintenance at any time. The metallic vapors eroded from the
contact surfaces during high current interruption remain in the

chamber and are deposited on metal shields thus insuring a

high dielectric value of the vacuum and the walls of the

interrupter.

11.1.2 Trouble Reporting

Although all reputable manufacturers design their products to

perform satisfactorily with a minimum of problems, the IEEE

Switchgear Committee, an organization of both users and

manufacturers, recognize the need for a common trouble

reporting format. A reproducible copy of this form is included
inside the rear cover of this book and is recommended for use

with any manufacturer’s circuit breakers.

The intent is for each maintenance organization to keep

specific problem files with this information documented.
If the problem is serious or repetitive, a summary should be

sent to the appropriate manufacturer for action. The level of

detail included on the form is considered very desirable so

that the manufacturer’s investigator may more thoroughly

understand and solve the reported problem.

11.2—Service Conditions

The frequency of required maintenance depends on

the severity of the service conditions of the switchgear

application. If the service conditions are mild, the interval

between maintenance operations may be extended to 10
years or 2,500 no load or 200 normal load switching

operations. Mild service conditions are defined as an

environment in which the switchgear is protected from the

deleterious effects of conditions such as:


Salt spray

Changes in temperature that produce condensation

Conductive and/or abrasive dust

Damaging chemicals and fumes

Vibration or mechanical shock
High relative humidity (90%)
Temperature extremes (below –30

°

C or above +40

°

C)

11.3—Fault Interruptions

The erosion rate of the primary contacts in the vacuum

interrupters is very low for normal load switching operations.
However, fault current interruptions at or near the breaker

rating may result in appreciable contact erosion. With frequent

fault interruptions it is necessary to perform maintenance

based on the number of interruptions. After 15 full fault

interruptions the following should be performed:


1. Contact erosion check.

2. Wipe and gap check

3. Vacuum interrupter integrity test.

11.4

Contact Erosion

Check in the breaker-closed condition per PRIMARY

CONTACT EROSION section 8.1. When erosion reaches

.125 inch, the interrupter should be replaced.

11.5—Transfer Finger Wear

With the breaker open, examine the moving contact rod

projecting below the transfer fingers (10, Figure 6). Wipe

off the lubricant in order to see the metal surface condition.

The finger locations should present a burnished silver contact

without copper appearance at more than one location. If

copper is visible at more than one location per pole or the
silver plating is torn, the interrupter assembly should be

replaced. Re-lubricate with 0282A2048P009.

11.6—Mechanism

Check all items covered in INSTALLATION and readjust or
tighten hardware as required. Lubricate as recommended

under LUBRICATION.

11.7—Primary Insulation Parts

Using dry, non-linting cloth or industrial-type wipers, clean
accessible insulation surfaces on the interrupter supports

and operating rod insulators. In service locations where

contamination is heavy or external flashovers, have occurred

during interrupter high-potential testing, remove the

interrupter assemblies per the procedure in REPAIR AND

REPLACEMENT and clean the inside surfaces of the
interrupter supports and the outer insulation surfaces of the

interrupters. Removal and reassembly of interrupter

assemblies will normally not require adjustment due to the

design of the interrupter operating rod insulator connection.

They should be returned to the same phase location from

which they were removed.

Advertising