GE Industrial Solutions Entellisys 4.0 System Test Kit User Manual User Manual

Page 25

Advertising
background image

Test Menu

25

Pre-defined values for Overcurrent Protection tests

Test results

Test Selection

Specifies the type of test to perform. Operator selectable.

Only enabled protection functions for the selected circuit breaker are
provided in drop-down.

Pre-Defined Settings

Displays the pre-defined fault levels to be injected for the test and circuit
breaker selected. Levels for Prefault, Fault, and Post faults are described in
Table 1-4.

These values are determined with respect to the circuit breaker selected and
its protection settings.

Fault Phase

The phase(s) for fault injection. Operator selectable.

Options for LT, ST, IOC Test Selection is: Phase A, Phase B, Phase C, Phase A &
B, Phase B & C, Phase C & A, Phase A, B & C

Option for GF Test Selection: Phase A, Phase B, Phase C, and Neutral

Table 1-4 Pre-defined values for Overcurrent Protection tests

Type of Test

Prefault
(for all Phases)

Fault
(for selected Phases)

Post Fault
(for all Phases)

Long Time

80.00% of LT Pickup

135.00% of LT Pickup

0% of LTPickup

Short Time

80.00% of ST Pickup

110.00% of ST Pickup

0% of LTPickup

Instantaneous

80.00% of IOC Pickup

110.00% of IOC pickup

0% of LTPickup

Ground Fault

40% of CT

110.00% of GF Pickup

0% of GF Pickup

Table 1-5 Test results

Time Stamp Table

Provides a time stamp history of the Breaker Status (Open or Closed) and the
Breaker Actuation device involved in the trip (Flux Shifter or Shunt Trip).

Expected Trip Time

Expected trip time automatically calculated from the pickup & delay band settings
and circuit breaker clearing time.

Observed Trip Time

Observed trip time displayed after the test is performed.

Test Summary LED

Specifies the test results by comparing the observed trip time with the expected
trip time.

Green

Successful (within +/– 20% of expected time)

Red

Unsuccessful

Gray

Test Aborted

Table 1-3 Test setup field description