System Test Kit

62

OverCurrent Test

Pre-Defined Overcurrent Test-
Short Time
/Instantaneous/Ground Fault
feature grayed out in Test
Selection in pre-defined tests

Protection elements not optioned
and/or enabled for the circuit
breaker selected.

Verify that the Protection enabled
for that circuit breaker in system
based on Table 1-4.

Incorrect Switchgear Configuration
used?

Check if settings downloaded were
same as in HMI.

Observed trip time reads zero

Test cable not connected to either
the test kit or the EntelliGuard
Messenger.

Verify the test kit connector is
attached to the desired circuit
breaker.

User-Defined Mode—Trip module
displays as No trip

Verify that the fault current entered
is greater than any of the LT/ST/IOC
Pickups.

User-Defined
Overcurrent—% Test Results
button grayed out

Test has not been run yet.

Test was aborted.

Pre-Defined Overcurrent
Protection—Test Summary is
grayed out

Test has not been run yet.

Test was aborted.

Pre-Define Overcurrent
Protection test failed
unexpectedly

Gear is operating in a different
topology than what the test kit
expects

Download settings from the HMI
again and repeat

Automatic Trip Time
Curve—Ground Fault curve
feature grayed out in select curve
type

Ground fault is not enabled for the
selected circuit breaker.

% Error is displayed as 100

Verify that the System Test Kit cable
is connected to the selected circuit
breaker on which the test is
performed and that observed trip
time is not zero.

% Error is displayed as ___

Verify that the point tested is IOC
trip and that trip time is less than
50/60 ms.

Table 1-20 Troubleshooting

Error

Potential Cause

Suggested Fix