Test Menu
29
Test results
Prior to a test the “Test Results” button will be grayed out.
After a test is performed, the “Test Results” button will display. Once pressed, the following is
displayed:
Figure 1-14 Overcurrent Protection Test Results
Phase Angle
Phase angle to be injected. (Range between –360° to +360°)
Expected Trip Module
Type of trip that should be observed, calculated from the operator-entered
fault levels.
Expected Trip Time
Trip time that should be observed, calculated from the operator-entered
fault levels.
Pre-Fault Time
The time duration Pre-Fault levels will be injected from test kit. Operator
selectable.
Fault Time
The time Fault levels will be injected. Operator selectable.
Post-Fault Time
The time duration Post-Fault levels will be injected. Operator selectable.
User-Defined Test Settings
Displays the currents and voltages that will be injected, calculated from the
operator's selections (for the Fault Level currently displayed).
Table 1-6 Test setup field description