GE Industrial Solutions Entellisys 4.0 System Test Kit User Manual User Manual

Page 37

Advertising
background image

Test Menu

37

This screen has the following selections and controls available. A user can perform either trip or
no trip single point protection relay function tests at the Messenger.

Table 1-9 Selections and controls

Test Name

Unique test identifier, assigned by the test kit, generated by the type of test
selected and the date the test is performed.

Operator

Operator name can be entered here for the Reports. (20-character limitation)

Test Description

Operator enters test description to be stored in the log file. (150-character
limitation)

Breaker Trip

Specifies whether the test will physically trip the circuit breaker.

;

– Circuit Breaker will Trip

†

– Circuit Breaker will not Trip

Ground Fault

Allows users to temporarily Defeat Ground Fault during the test, or to
Resume/Run Ground Fault as normal during the test. Ground Fault must be
defeated for single phase tests—otherwise a trip on Ground Fault will occur.

;

– GF will Resume/Run as Normal.

†

– GF will be temporarily defeated during the test period.

Note: After the test has concluded, Ground Fault will resume automatically.

This feature is enabled only when Ground Fault is enabled in the selected
circuit breaker.

Compartment #

Switchgear compartment number of the circuit breaker selected for testing.

Breaker Selection

The circuit breaker to perform the test.

Test Selection

Test Selection will let the type of protection fault be generated.

Breaker Settings

Circuit Breaker settings will display the current settings of that selected circuit
breaker.

Pre-defined Settings

This table displays the amount of test kit voltages that will be injected with
respect to the present settings of the selected circuit breaker.

Fault Phase Requirement

Displays the present Fault Phase Requirement for the selected Relay
protection:
One phase is above the pickup threshold.
Two phases are above the pickup threshold.
Three phases are above the pickup threshold.

Breaker Settings

This will display the current circuit breaker settings on which the test will be
performed.

Overvoltage Settings

This will display the current overvoltage settings of the system.

Undervoltage Settings

This will display the current undervoltage settings of the system.

Over Frequency Settings

Over Frequency settings will be displayed depending on the setting from
CCPU.