System Test Kit

38

Test results

Under Frequency Settings

Under Frequency settings will be displayed depending on the settings from
CCPU.

Phase Loss settings

Phase Loss settings will be displayed depending on the settings from CCPU.

Power Reversal

Power Reversal settings will be displayed depending on the settings from
CCPU.

High Current

High Current Settings will be displayed depending on the settings from CCPU.

Pre-Defined Settings

Depending on the current Messenger settings, Selected Level, Phase selected,
Frequency or Multiplier value IA, IB, IC, IN, VA, VB, VC will be calculated and
displayed on the screen.

Table 1-10 Test results

Time Stamp Table

Once the test is performed, it displays the time stamping of circuit breaker
status and the device that actuated the circuit breaker (Flux Shifter or Breaker
Open).

Expected Trip Time

Expected trip time automatically calculated from the pickup, delay band
settings, and circuit breaker clearing time.

Observed Trip Time

Observed trip time displayed after the test is performed.

Test Summary LED

Specifies the test results by comparing the observed trip time with the
expected trip time.

Green

Successful (within +/– 20% of expected time)

Red

Unsuccessful

Gray

Test Aborted

Table 1-11 Default values for pre-defined relay protection tests

Type of Test

Prefault

Fault

Post Fault

Over Frequency

System Frequency

Pickup *1.01

System Frequency

Under Frequency

System Frequency

Pickup * 0.99

System Frequency

Overvoltage

100% of PT

Pickup * 1.05

96% of PT

Undervoltage

100% of PT

Pickup * 0.95

100% of PT

Phase Loss

0%

Pickup + 1%

0%

Power Reversal

10 KW Positive Power

Pickup * 1.1 Reverse Power

10 KW Positive Power

High Current

Pickup * 0.5

Pickup * 1.1

Pickup * 0.5

Table 1-9 Selections and controls