3.4

UPS PARALLELED ON THE SAME BATTERY

NOTE !

A parallel system with a Common Battery for two or more UPS, requires a particular
installation and adequate setting of some parameters, (accessible only through
password), and can therefore only be done by a qualified GE engineer.


Usually each UPS Unit runs with its own Battery.
In case of parallel units running with a Common Battery (max. 4 UPS - see Fig. 3.4-1), the sharing circuit
between the individual UPS is integrated in the communication bus of the system in order to assure an
equal sharing of the Rectifiers output currents.

Fig. 3.4-1 Diagram RPA system with UPS on common battery

1 –

2 –

3 –

4 –

5 –

6 –

7 –

8 –

Rectifier

Inverter

Automatic Bypass

Manual Bypass

Mains Power

Load Bus Bar

Branch circuit protection

Battery


Pay attention to the following recommendations:
x

The units delivered for this functioning mode needs a special parameters setting, so they must be
prepared in advance before the installation.

x

The installation must be performed only with the UPS system completely shut down.

x

The AC Rectifiers input power (5) must be the same, with clockwise phase rotation for each unit.

x

Each Rectifier must be set for the same floating DC voltage and the same Battery current limitation.

x

It is mandatory to install the fuses / MCCB (7) on each line connecting the Rectifiers to the common
Battery for maintenance / safety reasons (see Section 4.7.2).

x

In case a unit must be powered down for maintenance, switch-OFF the concerned unit before open
the DC fuses / MCCB on the Battery line (7).

x

If an emergency generator set supplies the UPS, and the free contact “Generator ON” is connected
to the Customer Interface, connect a separate NO free contact on each parallel unit.

x

Do not connect the temperature sensor for automatic battery floating voltage compensation.

x

Do not enable the function Boost charge.