Operating Manual LP 33 Series 50 & 60 kVA

3.

Switch On the output switch Q1 (Pos. I).

The output will be supplied by the mains through the bypass.

LP 33 60kVA

APPLICAT. ON UTILITY

= xx%

Verify, selecting the screen METERING/Udcp and Udcn, that the
booster voltage has reached about 215 VDC.

Udcp=215V Udcn=215V
Ubp=164V

Ubn=164V F

Charge level

= 100%

Autonomy =

xxxmin

4. Switch On the inverter entering the screen:

MENU/COMMAND MENU/INVERTER ON

COMMAND MENU

INVERTER ON *
INVERTER OFF

Some seconds later the load will be transferred on inverter
and the main screen will display: APPLICATION ON UPS

LP 33 60kVA

APPLICATION ON UPS

= xx%

5.

Operation mode selection.

LP 33 Series is delivered normally selected for permanent VFI operation.

ECO Mode can be enabled and the ECO START time & ECO STOP time can be programmed for each
day of the week (see Section 6.3.1-5).

END OF PROCEDURE






NOTE !

Even if the UPS is delivered with fully charged batteries, they could be partially
discharged during transportation or storage.

It is recommended to recharge batteries for few hours in order to provide complete
battery
energy stored to the load in the event of mains failure.