Operating Manual LP 33 Series 50 & 60 kVA

Code

Message

Meaning

4362

INVERTER

OFF

The command to switch OFF the inverter has been done by
the control panel or automatically for alarm detection.

4411

BYPASS MAINS

OK

Bypass input mains is again within the admitted tolerance
(voltage, frequency and phase).

4500

COMMAND

LOAD OFF

Disconnection of the load by opening K4, K6 and K7 for:
EPO / Total Off / Overload / Stop operation.

4521

NO BYPASS

POWER

With the load supplied by electronic bypass, a mains failure or
K6 opening occurred.

4534

MULTIPLE LOAD

TRANSFER

2 transfers inverter-mains have been detected in a short time,
defined by respective parameter (default 30 seconds).

4535

BYPASS

LOCKED

Transfer on mains not enabled due to settings of respective
parameters. Contactor K6 is open.

4536

BYPASS

FREE

Settings of respective parameters enable bypass transfer on
mains.
Contactor K6 can be closed.

4561

TOTAL

OFF

Push-button Total Off behind the front door has been pressed,
with the output circuit breaker Q1 closed.

4562

DETOUR

ON

This indicates that manual bypass Switch Q2 has been closed
(ON), UPS is in service mode.

4564

DETOUR

OFF

This indicates that manual bypass Switch Q2 has been
Opened (OFF), UPS is out-of service mode.

4567

COMMAND

LOAD ON MAINS

The control unit received a command to transfer the load on
mains.

4568

COMMAND

LOAD ON INVERTER

The control unit received a command to transfer the load on
inverter.

4572

NO MORE

OVERLOAD

End of the overload condition previously detected with alarm
4570.

4580

INVERTER AND

MAINS SYNCHRONIZED

The voltages of inverter and mains bypass are synchronized.

4582

COMMAND NOT TO

SYNCHRONIZE

Command not to synchronize with mains has been done for:
mains bypass out of tolerance (4410) or setting respective
parameters.

4583

COMMAND TO
SYNCHRONIZE

Command to synchronize with mains has been done for:
mains BP OK (4410) or setting respective parameters.

4600

COMMAND

UPS ON

The ECO Mode function has been disabled or the programmed
time is expired.
The UPS returns to VFI Mode supplying the load normally by
inverter.

4601

COMMAND UPS

STAND BY

The function ECO Mode is enabled, and according to the time
program the UPS will run in ECO Mode, supplying the load
normally by mains.