Modifications reserved

Page 21/66

OPM_LPS_3UO_80K_M10_1US_V010.doc

User Manual LP33 Series 80 & 100 UL S1

5.2 TABLE OF FUNCTIONS AND INDICATIONS ON CONTROL PANEL

Key to switch the Inverter ON ( I )

Key for Inverter shutdown ( O )
Press key to transfers the Load to Utility.
Keep pressed for 5 seconds to shutdown the Inverter.
This key is also used as the EPO (Emergency Power Off) reset.

Key “Load Off”
The key “Load Off” is protected by a transparent cover.
By pressing it, you immediately separate the UPS from the Load.

It is possible to activate the command “Load Off” using the following screen:

COMMANDS / REQUEST TOTAL OFF. See Section 6.5.

Attention: “Load Off” cannot disconnect the UPS from the Load with Q2 closed.

`

Home\Commands

COMMANDS

RESET TOTAL OFF

REQUEST TOTAL OFF

To reset “Load Off”

Restore the command “Load Off”
by entering the screen:
COMMANDS / RESET TOTAL OFF

V



For Parallel System: if “Load Off” is pressed on one unit connected to

the parallel bus (switch Q1 closed), all the units are separated from the load.
The “Load Off” reset must be done only on one unit connected to the parallel bus
(switch Q1 closed).

NOTE !

Special care must be taken in using this command, in order to
avoid accidental load
disconnection.