LP33 Series S1 100KVA

UPS Model

UPS series number

UPS nominal rating (kVA)

Battery level LED

All

LED light indicate a battery autonomy of 100%.

LED A

Fixed:

indicates battery autonomy between 6% and 25%.

Blinking:

indicates battery autonomy ≤5%.

LED A, B

Indicate battery autonomy between 26% and 50%.

LED A, B, C

Indicate battery autonomy between 51% and 99%.

Min:

Battery autonomy time in minutes estimates with actual load.

Load level LED

All LED OFF indicate a load status at ≤25%.
LED A

Indicates a load level between 26% and 50%.

LED A, B

Indicate a load level between 51% and 75%.

LED A, B, C

Indicate a load level between 76% and 100%.

LED A, B, C, D

Indicate a load level between 101% and 124%.

LED D blinking

Indicates a load level ≥125%.

Fig. 6.1-2 LEDs on synoptic diagram

LEDs on synoptic diagram

LED 1 Utility

rectifier

OK

LED 2 Utility

bypass

OK

LED 3 Rectifier

ON

LED 4 Discharging

battery

LED 5 Booster

ON

LED 6

Charge battery ON

LED 7 Inverter

available

LED 8 Inverter

ON

LED 9 Q1

closed

LED 10 Automatic

bypass

ON

LED 11

Manual bypass Q2 ON

LED 12

Load on UPS

Examples of typical scenarios in the synoptic diagram:

Load supplied by Inverter

Load supplied by Automatic Bypass

Load supplied by Manual Bypass Q2

Load supplied by Battery