User Manual LP33 Series 80 & 100 UL S1

Code

Alarm

Meaning

4301

INVERTER FUSES FAILURE

Inverter output fuses blown.
Signaled by electronic detector.
Inverter can be started manually after replacement of
fuses.

4304

K7 CLOSING FAILURE

K7 not closed despite a closing command being done.
Signaled by auxiliary contact.
The load will be supplied by utility.

4305

K7 OPENING FAILURE

K7 not open despite an opening command being done.
Signaled by auxiliary contact.
The load will be supplied by utility.

4312

INV. VOLTAGE OUT

OF TOLERANCE

Inverter output voltage is out of the tolerances defined in
respective parameter (±10%).
Inverter is switched OFF.

4320

ISMAX DETECTION

Detection of inverter bridge (Is) current limitation cause
inverter OFF and possible automatic restart.
After 3 times inverter switches OFF for persistent Is max
detection in time.
Inverter switch OFF, and it can be restarted manually.

4340

INVERTER CONTROL FAILURE

The slave oscillator is not synchronized with the master,
thus causing the shutdown of it’s inverter.

4347

OSCILLATOR FAILURE

Auto calibration of the Inverters free run frequency was not
possible.
The oscillator frequency of this unit is out of tolerance.

4402

RECTIFIER CANNOT BE

TURNED ON

The rectifier cannot be turned on because the DC link
voltage has not reached the requested value.

4404

K6 CLOSING FAILURE

K6 not closed despite a closing command being done.
Signaled by auxiliary contact.
The load cannot be supplied by electronic bypass.

4405

K6 OPENING FAILURE

K6 not open despite an opening command being done.
Signaled by auxiliary contact.

4410

BYPASS UTILITY OUT

OF TOLERANCE

The utility bypass voltage is out of the tolerances (±10%).
K6 opens, synchronization with utility is inhibited and
transfer to utility is blocked.

4520

NO INVERTER POWER

The load supplied by utility is over 100%.
The load remains blocked on utility as long as alarm
overload is active.

4530

LOAD LOCKED ON UTILITY

Load is locked on utility because 3 transfers on utility have
been detected in a short time (default 30 seconds).
Transfer will be free again after a time defined by
respective parameter (default 30 seconds).

4531

LOAD ON UTILITY

BY ERROR DETECTOR

Load is transferred to utility because the error detector
detected a disturbance on the output voltage.

4563

EMERGENCY OFF ACTIVATED

Alarm after detection of an Emergency OFF from an
external safety device connected on Customer Interface.
Consequently K4, K6 and K7 open and shut down inverter,
booster and rectifier.

4570

OVERLOAD

The UPS-System is in an overload condition >125% on
inverter, or >150% on utility.
A sequence of “stop operation” starts.
Time out depending on load quantity.