GE Industrial Solutions LP33 Series 80 & 100 User Manual User Manual

Page 31

Advertising
background image

Modifications reserved

Page 31/66

OPM_LPS_3UO_80K_M10_1US_V010.doc

User Manual LP33 Series 80 & 100 UL S1

Code

Alarm

Meaning

4571

OVERLOAD: LOAD ON UTILITY

With utility bypass supply available and load >115%, the
load is transferred on utility.
Load will be transferred again automatically on inverter
when load will be <100%.

4581

INVERTER AND UTILITY

NOT SYNCHRONIZED

The voltages of utility and inverter are not synchronized,
which causes the opening of K6.

4697

BATTERY OVERTEMPERATURE

The battery temperature exceeds the value inserted in
parameter.
Disabled with parameter (service only).

4698 BATTERY POWER INSUFFICIENT

In case of utility failure, with the actual load, the autonomy
time would result below “stop operation” time (default 3
minutes).

4700

DC LOW

Battery voltage is at the lowest limit.
Shutdown of inverter until the battery voltage reaches the
value in respective parameter.

4900

LOAD LOCKED ON INVERTER

The load is locked on Inverter following 3 load transfers
within 30 seconds.
After time out of the value in respective parameter (default
30 seconds), bypass will be free.

4955

OVERTEMPERATURE

An over temperature condition has been detected on
inverter.
Elapsed “stop operation” time, inverter shutdown.
With utility available, load is transferred on utility.

4998

LOAD OFF DUE TO

EXTENDED OVERLOAD

Load OFF after time-out of “stop operation” for overload on
inverter or bypass (time depending on the % of overload).

4999

LOAD OFF DUE

TO LOW BATT. OR TEMP.

Load OFF after time-out of “stop operation” with missing
utility due to battery low voltage or over temperature
condition.