OPM_LPS_3UO_80K_M10_1US_V010.doc

User Manual LP33 Series 80 & 100 UL S1

7.1 PROCEDURES FOR SINGLE LP33 Series 80 & 100


7.1.1 Start-up of the LP33 Series 80 & 100

WARNING !

Before connecting hazardous voltages, make sure that:
The connection to the electrical system has been performed by QUALIFIED

PERSONNEL;

The equipment frame has been correctly grounded to the main earth;
Make sure that utility input protection is removed;
All the panels removed to allow the UPS connection have been correctly reinstalled;
The UPS switches Q1 and Q2 are OFF (Pos. 0);
The “Battery Breaker” of the battery cabinet is OFF (Pos. 0).


This procedure must be performed for the first start-up following the installation, with the UPS
completely switched OFF and not powered.

This procedure presupposes that the Load is not yet supplied by the UPS system.

NOTE !

The UPS can be started-up using the Battery Supply in case the Input Utility should be
unavailable.
To avoid an incidental Battery
discharge, it is recommended to proceed to the UPS
start-up having the Input Utility
available.

Open the front door and make sure that:

All the connections to the input/output terminals of the UPS have been made correctly.

The safety screens are fixed in their position.

The switches Q1 and Q2 are open (Pos. O) and the Battery Breaker of the Battery Cabinet (option) is
OFF (Pos. 0)
.

LEDs on synoptic diagram

Q2

I ON

0 OFF

Q1

I ON

0 OF

F

Q1

UPS output switch

Q2 Manual

bypass

switch

LED 1

Utility rectifier OK

LED 2

Utility bypass OK

LED 3

Rectifier ON

LED 4

Discharging battery

LED 5

Booster ON

LED 6

Charge battery ON

LED 7

Inverter available

LED 8

Inverter ON

LED 9

Q1 closed

LED 10 Automatic bypass ON

LED 11 Manual bypass Q2 ON
LED 12 Load on UPS

Key Key

Key LED LED LED

Inverter ON

Inverter OFF

Load Off

Stop Operation

Alarm

Operation

Continue