GE Industrial Solutions LP33 Series 80 & 100 User Manual User Manual

Page 37

Advertising
background image

Modifications reserved

Page 37/66

OPM_LPS_3UO_80K_M10_1US_V010.doc

User Manual LP33 Series 80 & 100 UL S1

`

Home\Setup\User

MODEM

Tel 2

:

2

Tel 2 enabled

:

N

Tel 3

:

3

Tel 3 enabled

:

N

Tel 4

:

4

Tel 4 enabled

:

N

V

Modem screen 2

Tel 2

It records the second dial-out number.

Tel 2 enabled

This parameter Y/N specifies if the

second telephone number will be used for dial-out.

Tel 3

It records the third dial-out number.

Tel 3 enabled

This parameter Y/N specifies if the third

telephone number will be used for dial-out.

Tel 4

It records the fourth dial-out number.

Tel 4 enabled

This parameter Y/N specifies if the fourth telephone number will be used for dial-out.

`

Home\Setup\User

DISPLAY

UPS name

:

LP Series

Language :

ENGLISH

Contrast

V

LCD Display screen

UPS Name The user can choose the name of the UPS
model shown on the main page (max. 9 characters).

Language This parameter allows the choice of language
used to display the information.

Valid choices are: English, German, Italian, Spanish, French,

Finnish, Polish, Portuguese, Czech, Slovakian, Chinese,

Swedish, Russian and Dutch.

Contrast

This parameter controls the contrast of the

LCD screen in ten steps (0 – 9).

`

Home\Setup\User

ECO MODE

Enabled :

N

DAY OF WEEK

d1 d2

d3

d4

d5

d6

d7

HOURS / DAY

24 24 12 12 12 12 12

ECO MODE screen

This screen is enabled only for a single UPS, not for an RPA
Parallel System
.

Enabled

This parameter (values Y/N) enables or

disables the operation in ECO Mode.
If the value is Y and the current time is in the interval for the
current day, the ECO Mode is active.

The activation / deactivation of ECO Mode is indicated each
time in the event list.

In order to check the inverter function, at least 1 minute of VFI mode must be programmed during the week (the
Y/N parameter is automatically disabled if this condition is not satisfied).
In case this minimum time in VFI mode is not respected, the ECO Mode will be disabled.
If the value is N, the UPS is normally operating in VFI / double conversion mode at all times.

DAY OF WEEK (d1 to d7): Enabling time in function of weekdays

For the weekdays from d1 to d7 (Saturday to Friday) the edit mode (edit day) allows to define time intervals when
the UPS is operating in ECO Mode.

The hour is given in 24-hour format.

These intervals are defined by:

ECO Mode START:

The hour of the day after which the ECO Mode is enabled.
The ECO Mode is enabled until the following ECO Mode STOP time is reached (the ECO Mode

STOP time of the same day if this is later than the ECO Mode START time, the ECO Mode
STOP
time of the following day otherwise).

ECO Mode STOP:

The hour of the day before which the ECO Mode is enabled.

The ECO Mode is enabled starting from the preceding ECO Mode START time (the ECO Mode START time of the

same day if this is earlier than the ECO Mode STOP time, the ECO Mode START time of the previous day otherwise).

Identical times for ECO Mode START and ECO Mode STOP maintain the existing mode only in case the previous

command was ECO Mode START and the following command will be ECO Mode STOP.

HOURS / DAY:

The number of ECO Mode hours per weekday (from d1 - Saturday to d7 - Friday) is displayed in the operation
mode parameter window (ceiling value).