This UPS is only designed to operate in a wye-configured electrical system with a
solidly grounded neutral.

In case of 3-wire utility input the following solutions are possible:
1- Connection of a “3-wire kit” between Utility Input and Neutral of the output

transformer.
Attention:

With this configuration, load can only be connected phase-phase.
Absolutely no load connection permitted to the Neutral of the
output transformer.

In a RPA configuration with 3-wire kit,
it’s most important to connect the
Neutrals of the UPS outputs together
(see Fig .3.8.3-2).


Cable section for this connection shall
be not less then AWG 1.

Fig. 3.8.3-2 3-wire kit for RPA Parallel System

2- Bypass

transformer.

In this case the Neutral of wye secondary winding must be connected to the
Neutral of the output transformer.

Contact your Service Center for additional solutions.