COMMUNICATIONS GUIDE

RS485 INTERFACE (MODBUS RTU)

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – COMMUNICATIONS GUIDE

9

Operation Code

Description

1

Reset

96

Clear Last Fault Data Prompt

97

Reset MWh and Mvarh Meters

99

Clear Trip Counters

100

Clear Event Records

102

Clear Maintenance Timer

120

Trigger Waveform Capture

161

Reload Factory Setpoints 2

162

Reload Factory Setpoints 1

163

Restore to setpoint acess only

181

MX350 Test

182

MX350 Test - Fast Test

183

MX350 Test - Xfer Load

184

MX350 Test - No Xfer

185

MX350 Test - Bypass Exerciser

186

MX350 Test - Cancel Exerciser Bypass

188

MX350 Test - Cancel Bypass

189

MX350 Message - Bypass

190

MX350 Message - Yes

191

MX350 Message - No

192

MX350 Message - Escape

193

MX350 Message - Cancel

194

MX350 Message - Silence

195

MX350 Message - Reset

The following commands can only be performed using function code 05H
196

Reset Time S2 Available Counter

197

Alarm Silence

198

Control to bypass W-timer

199

Control to bypass T-timer

200

Net Ctrl Test on No load

201

Fast Load Test Control

202

Regular Load Test Control

203

Auto/Manual retransfer to S1

204

Auto/Manual transfer to S1/S2

205

Net Ctrl Load Shed for S1

206

Net Ctrl Inhibit Transfer to S2

207

Net Ctrl Inhibit Transfer to S1

208

Net Ctrl Transition Mode Selector

209

Command to Bypass R50

210

Confirm Bypass R50

211

Cancel Bypass R50

223

Net Ctrl Test on Load

224

Net Ctrl Transfer Commit